176                                                 Boiler Plant and Distribution System Optimization Manual



































                                     Figure 10.77—vent condenser opportunities. Sometimes there
                                     is a lot of pure steam available leaving plants containing a lot
                                     of energy.


                10.  WASTE HEAT FOR PROCESS                         11.  RECOVER STEAM AND HEAT FROM
                     APPLICATIONS                                        HIGH PRESSURE CONDENSATE
                                                                         RECOVERY SYSTEMS
                Cost
                                                                         This is usually a design function but if low
                     Moderate
                                                                    pressure  steam  or  hot  water  is  being  wasted,  it
                                                                    may be a good candidate for heat recovery.
                Potential Savings
                     High
                                                                    12.  INSTALL A CONDENSING ECONOMIzER
                Description                                              TO HEAT MAKE-UP WATER
                     If  waste  heat  can  not  be  recycled  into  the
                                                                         With natural gas fuel a deep economizer Tef-
                boiler process, then it can be transferred for other
                                                                    lon coated tubes, glass, stainless steel or titanium
                applications like water heating and warm air for
                                                                    that condenses flue gas water vapor can capture a
                drying processes. The best choice is to return the
                                                                    lot of wasted energy.
                heat to the boiler itself, to eliminate load match-
                ing and other complications.
                                                                    13.  ExTRACT COMBUSTION AIR AT THE
                Advantages/Disadvantages
                                                                         ROOF LEVEL OF THE PLANT
                     The complexity of transporting the heat to its
                point of use may be expensive. When waste heat           The high locations in boiler rooms can get quite
                is returned to the boiler, automatic load matching   hot. Hot air from this location and from around the
                usually occurs. When using waste heat for pro-      exhaust stacks can be drawn into the combustion
                cess loads, the demand may not always match the     air system. A percent or so efficiency improvement
                boiler loads and special controls may be needed     might be available from such measures.