Page 255 - Chemical Process Equipment - Selection and Design
P. 255

224  HEAT TRANSFER  AND  HEAT  EXCHANGERS

                 TABLE 8.22.  Specifications of Thicknesses of Pipe Insulation   expanding to a low pressure at which the solution becomes cold
                           for Moderate and High Temperatures, in Single   and flashed.
                           or Double Strength as May Be Needed      3.  Steam jet  action in which  water  is  chilled by  evaporation in  a
                 (a)  Insulation of 85% Magnesia or Equivalent up to 600°F   chamber maintained  at low  pressure  by  means of  a  steam jet
                                                                      ejector. A temperature is 55°F or so is commonly attained, but
                     Pipe Size    Standard Thick   Double Standard    down  to  40°F  may  be  feasible.  Brines  also  can  be  chilled by
                      (in.)           (in.)          Thick (in.)      evaporation to below 32°F.
                   1-112  or less      718            1-1 511 6        The unit of  refrigeration is the ton which is approximately the
                   2                 1-1/32           2-5/32
                   2-  112           1-1/32           2-5/32        removal  of  the  heat  of  fusion  of  a  ton  of  ice  in  one  day,  or
                   3                 1-1/32           2-5/32        288,000 Btu/day, 12,000 Btu/hr, 200 Btu/min.  The reciprocal of  the
                   4                 1-118            2-  1 /4      efficiency,  called the coefficient of  performance (COP) is the term
                   5                 1-118            2-5/16        employed  to  characterize  the  performances  of  refrigerating
                   6                 1-118            2-5/16        processes:
                   8                 1-114            2-112
                   10                1-114            2-112            COP
                   12-33             1-112            3
                                                                         - energy absorbed by the refrigerant at the low temperature
                                                                         -
                 (b)  Molded  Diatomaceous Earth  Base  Insulation, to  1900°F.     energy input to the refrigerant
                 Single or Double Thickness as Needed
                                                                    A  commonly  used  unit  of  COP  is  (tons  of  refrigeration)/
                           Pipe Size
                             (in.)        Thickness (in.)           (horsepower input).  Some of  the  refrigerants suited to  particular
                                                                    temperature ranges are listed in Tables 1.10, 8.23, and 8.24.
                                                            ~~
                             1-112     2         2
                             2         1-114     2-  1  /8          COMPRESSION REFRIGERATION
                             2-112     1-5/16    1-13/16
                             3         1-9/16    2-1/16             A  basic  circuit  of  vapor  compression refrigeration  is  in  Figure
                             4         1-9/16    2-1/16             8.24(a). After  compression, vapor is condensed with water cooling
                             5         1-112     2                  and then expanded to a low temperature  through a valve in which
                             6         1-112     2-1/16             the  process  is  essentially  at  constant  enthalpy.  In large  scale
                             8         1-112     2
                            10         1-9/16    2-118              installations  or  when  the  objective  is  liquefaction  of  the
                            12         1-9/16    2-118              “permanent”  gases, expansion to lower temperatures is achieved in
                            14-33      1-112     2                  turboexpanders from which power is recovered; such expansions are
                                                                    approximately isentropic.  The  process  with  expansion through  a
                 (c) Combination Insulation, inner Layer of Diatomaceous Earth   valve  is  represented  on  a  pressure-enthalpy  diagram  in  Figure
                 Base, and Outer of 85% Magnesia or Equivalent, for High Level
                 Insulation to 19OOOF                               8.24(b).
                                                                       A process employing a circulating brine is illustrated in Figure
                        Inner Layer             Outer Layer         8.24(c); it is  employed when  cooling is  required  at  several points
                                                                    distant  from  the  refrigeration  unit  because  of  the  lower  cost  of
                   Pipe Size   Thickness   Nominal Pipe   Thickness   circulation of  the brine,  and when leakage between refrigerant and
                     (in.)       (in.)      Size (in.)    (in.)     process fluids is harmful.
                 1-112  or less   2       no outer layer   -           For an overall compression ratio much in excess of  four or so,
                 2              1-114        4-  1 /2     1-112     multistage compression is more economic. Figure 8.24(d) shows two
                 2-  112        1-5/16       5           1-112      stages with intercooling to improve the capacity and efficiency of the
                 3              1-9/16       6           1-112      process.
                 4              1-9/16       7            1-112        Many  variations  of  the  simple circuits are  employed in  the
                 5              1-112        8           2          interest of  better  performance. The case of  Example 8.17 has two
                 6              1-112        9           2          stages of  compression but  also two stages of  expansion, a scheme
                 8              1-112        11          2          due  originally to Windhausen (in  1901). The flashed vapor of  the
                 10             1-9/16       14          2
                 12             1-9/16       16          2          intermediate stage is recycled to the high pressure compressor. The
                 14-33          1-112        17-36       2          numerical example shows that  an improved COP  is  attained  with
                                                                    the modified circuit. In the circuit with  a centrifugal compressor of
                    Data of an engineering contractor.              Figure 8.25, the functions of  several intermediate expansion valves
                                                                    and  flash drums are combined in a  single vessel with  appropriate
                 8.13.  REFRIGERATION                               internals called an economizer. This refrigeration unit is used with a
                                                                    fractionating  unit  for  recovering  ethane  and  ethylene  from  a
                 Process temperatures  below those attainable with cooling water or   mixture with lighter substances.
                 air  are  attained  through  refrigerants  whose low temperatures  are   Low  temperatures  with  the possibility of  still using  water  for
                 obtained by several means:                         final  condensation  are  attained  with  cascade  systems  employing
                                                                    coupled circuits with different refrigerants. Refrigerants with higher
                 1. Vapor compression refrigeration in which a vapor is compressed,   vapor  pressures  effect  condensation  of  those  with  lower  vapor
                   then  condensed  with  water  or  air,  and  expanded  to  a  low   pressures. Figure 8.26 employs ethylene and propylene in a cascade
                   pressure  and correspondingly low  temperature  through  a valve   for servicing the condenser of a demethanizer which must be cooled
                   or an engine with power takeoff.                 to -145°F.  A  similar process is  represented on a flowsketch in the
                 2.  Absorption  refrigeration  in  which  condensation  is  effected by   book  of  Ludwig  (1983, Vol.  1, p.  249). A  three  element cascade
                   absorption of vapor in a liquid at high pressure, then cooling and   with methane,  ethylene and propylene refrigerants is calculated by
   250   251   252   253   254   255   256   257   258   259   260