Page 256 - Chemical Process Equipment - Selection and Design
P. 256

8.13.  REFRIGERATION  225

                                                                               Critical point   Saturated liquid line
                                                                                       \
                                                                      Saturated vapor line
                                                                                                     arge
                                                                                                     heat
                                                                  m
                                                                  .-
                                                                  a
                                                                  u)
                                                                  5
                                                                  2
                                                                  fn
                                                                  E
                                                                  a
                                                                                Enthalpy, h  (Btu/lb)
                                                                                     (b)


















                                                                                   stage        stage
                           Brine pump                                                (d)
                                 (c)
                     figure  8.24.  Simpler circuits of  compression refrigeration  (see also Example 8.17). (a)  Basic circuit consisting of  a
                     compressor, condenser, expansion valve and evaporator (load). (b) Conditions of  the basic circuit as they appear on a
                     pl-essure-enthalpy diagram; the primed points are on the vapor-liquid  boundary curve. (c) Circuit with circulation of
                     refrigerated brine to process loads. (d) Circuit with two-stage compression and intercooling.




             EXAMPLE 8.117                                    recycled to the suction of  the high pressure stage while the liquid is
             Two-Stage  Propylene  Compression Refrigeration  with  Inter-   expanded to  16 psia  to provide the  needed  refrigeration  at  -9°F.
             stage Recyele                                    The ratios of refrigeration to power input will be compared without
          A  propylene  refrigeration  cycle  operates  with  pressures  of  256,   and with interstage recycle.
          64,  and  16psia.  Upon  expansion  to  64psia,  the  flashed  vapor  is   Basis: 1 Ib  of  propylene to the high pressure stage. Conditions

                                        High pressure
                                        stage
















                           I   '        Low pressure                        Enthalpy
                          Load          stage