Page 114 - Defrosting for Air Source Heat Pump
P. 114

106                                         Defrosting for Air Source Heat Pump

         4.3.2.3 Case 3

         Fig. 4.27 shows the variations of the predicted tube surface temperatures at the exit of
         each circuit during defrosting in Study Case 3. The simulation results showed that the
         defrosting durations were 172 s for Circuit 1, 182 s for Circuit 2, and 186 s for Circuit
         3, respectively. As shown in Figs. 4.20C and 4.24, when the modulating valve on Cir-
         cuit 1 was closed at 172 s into defrosting, its refrigerant mass flow rate was reduced to
         0 g/s. For the other two circuits, the refrigerant mass flow rates remained unchanged
         after the compressor speed was reduced by one-third. As seen, the surface temperature
         for Circuit 1 was reduced after closing the valve at 172 s, but those for Circuit 2 and
         Circuit 3 continued their increasing trend. Unlike the other two study cases, the
         defrosting duration for Circuit 3 or the ASHP unit was slightly increased by
         1–187 s, when compared with the results of the previous experimental study. At
         the same time, Δt was also slightly increased by 1–15 s, suggesting that the problem
         of uneven defrosting remained.
            The simulation results for the three study cases are summarized in Table 4.3,where
         the results of the previous experimental study are also included. To clearly illustrate the
         difference of these durations, the analysis on durations for the three study cases and
         the previous experimental and modeling studies are shown in Fig. 4.28.In this
         figure, the time difference in defrosting duration between the study case and the previ-
         ous experimental study, △dt, was used as a parameter to indicate the defrosting dura-
         tion. The bigger the value of △dt, the earlier the defrosting process of this study case
         was terminated. It can be seen from Table 4.3 and Fig. 4.28 that for the three study cases,
         Study Case 2 appeared to be the better one in terms of shortening the defrosting duration
         with the shortest duration of 179, 7 s earlier than the defrosting termination of the

                     12
                              Circuit 1     Circuit 2     Circuit 3
                     10 8  10.52 g/s
                   Refrigerant mass flow rate (g/s)  6 4  Stage 3: Decrease




                                                      and then fluctuate


                           Stage 1: Fluctuate
                     2
                                                    160 s
                                  70 s   Stage 2: Increase steadily 172 s
                     0
                         0   20  40  60  80  100  120  140  160  180  200
                                           Time (s)

         Fig. 4.24 Assumed refrigerant mass flow rate in the three circuits during defrosting in Study
         Case 3.
   109   110   111   112   113   114   115   116   117   118   119