Page 111 - Defrosting for Air Source Heat Pump
P. 111

Modeling study on uneven defrosting                               103

             (i) In the previous experimental study, the refrigerant mass flow rate in the three refrigerant
               circuits was assumed to be evenly distributed. The calculated refrigerant mass flow rates
               in the three circuits in the previous experimental study were derived following this
               assumption.
            (ii) In the three study cases, the refrigerant mass flow rate passing through a modulating valve
               to each circuit during defrosting was assumed to be proportional to the respective percent-
               age openings of the three modulating valves, under a constant total refrigerant flow rate.
               For example, when the percentage openings of the valves are 50% for the valve on Circuit
               1 and 100% for the valves on Circuits 2 and 3, respectively, the ratio of the three valves’
               openings is 1:2:2, and thus the percentage shares of the total refrigerant mass flow rate
               passing through the three modulating valves are 20%, 40%, and 40%, respectively.
               The assumed refrigerant mass flow rates to each circuit during defrosting in Study Case
               1 shown in Figs. 4.20A and 4.22 were derived following this assumption.
            (iii) In Study Case 2, the total refrigerant mass flow was evenly distributed to the other two
               refrigerant circuits during defrosting after the modulating valve on Circuit 1 was closed.
               As a result, the refrigerant mass flow rates to Circuit 2 and Circuit 3 were each increased
               by 50%, as illustrated in Fig. 4.20B.
            (iv) In Study Case 3, as the modulating valve on Circuit 1 was closed, the refrigerant mass flow
               in Circuit 2 and Circuit 3 remained unchanged as a result of compressor speed reduction
               by 33%.
            (v) The energy consumption on the compressor would decrease 33% as a result of a compres-
               sor speed reduction by 33%.
            (vi) When the tube surface temperature at the exit of a refrigerant circuit reached 24°C, the
               defrosting operation on that circuit was considered ended. The experiment conditions
               illustrated in Figs. 4.20B and C were derived following this assumption.
           (vii) The defrosting duration for the ASHP unit was the same as that of Circuit 3.


                      14
                                Circuit 1     Circuit 2     Circuit 3
                      12
                             10.83 g/s
                     Refrigerant mass flow rate (g/s)  8 6 4  10.10 g/s  R  > R  > R 1  Stage 3: Decrease
                      10
                             10.62 g/s

                                       3
                                          2


                                                         and then fluctuate
                             Stage 1: Fluctuate
                       2
                                     70 s  Stage 2: Increase steadily
                                                       160 s
                       0
                           0   20  40  60  80  100  120  140  160  180  200
                                            Time (s)

           Fig. 4.22 Assumed refrigerant mass flow rate in the three circuits during defrosting in Study
           Case 1.
   106   107   108   109   110   111   112   113   114   115   116