Page 142 - Defrosting for Air Source Heat Pump
P. 142

Investigation of effect on uneven defrosting performance          135


            Table 5.7 Energy performance analysis for the three experimental cases
            Item   Parameter                     Case 1  Case 2   Case 3   Unit

            1      The power input to compressor  111.0  112.6    140.3    kJ
            2      The power input to indoor air fan  6.3  1.7    1.6      kJ
            3      The power input to outdoor air fan  0  0       7.2      kJ
            4      The energy from the indoor air  609.9  538.6   663.0    kJ
            5      Total energy supply during defrosting  727.1  697.9  812.0  kJ
            6      Energy consumption on melting frost  307.6  323.3  313.0  kJ
            7      Energy consumption on vaporizing  55.0  48.9   66.0     kJ
                   the retained water
            8      Total energy consumption for  362.6   372.2    379.0    kJ
                   defrosting
            9      Defrosting efficiency         43.5%   53.3%    46.7%    –



              In this section, to decrease the flow path of downward-flowing melted frost due to
           gravity, the multicircuit outdoor coil was changed to be horizontally installed. In addi-
           tion, the operation of reversing the outdoor air fan and blowing the remaining water
           away was undertaken to decrease the total mass of the remaining water. Finally, the
           following conclusions were reached: (1) When a vertically installed multicircuit out-
           door coil in an ASHP unit was changed to horizontally installed, the defrosting effi-
           ciency increased from 43.5% to 53.3%, or at an increasing value of 9.8%. Meanwhile,
           the negative effects of melted frost downward flowing due to gravity were eliminated.
           The positive effects of a horizontally installed multicircuit outdoor coil on defrosting
           performance for an ASHP unit are obvious. (2) For an ASHP unit with a horizontal
           multicircuit outdoor coil, when the outdoor air fan was used to blow the melted frost
           during defrosting, the total mass of the retained water collected obviously decreased,
           from 566 g to 344 g, or 222 g less. However, the defrosting efficiency was not
           increased, but decreased from 53.3% to 46.7% due to the heat transfer being enhanced
           between the hot coil and the cold wind. Therefore, destroying the surface tension to
           enhance the melted frost’s local drainage as well as an outdoor coil structure adjust-
           ment and fin surface treatment may be a better choice. (3) To evaluate the energy con-
           sumption on heating the ambient air due to waiting for the other circuit to terminate its
           defrosting, the DEC was innovatively defined and first used here. The experimental
           results demonstrated that, to improve the defrosting performance, the DEC should
           also be improved. Therefore, there would be less energy consumed on heating the
           ambient air to wait for the other circuit’s defrosting termination. Furthermore, the
           DEC was suggested to be used as an index to evaluate the defrosting performance
           of an ASHP unit with a multicircuit outdoor coil. (4) During an operational cycle
           of frosting-defrosting for an ASHP unit, the frosting duration is always much longer
           than the defrosting duration. Consequently, frosting studies account for more impor-
           tant parts in studies of system performance improvement. Therefore, system frosting
           performance should also be studied for an ASHP unit with a horizontally installed out-
           door coil before a traditional vertical outdoor coil is changed to being horizontally
           installed.
   137   138   139   140   141   142   143   144   145   146   147