Page 145 - Defrosting for Air Source Heat Pump
P. 145

138                                         Defrosting for Air Source Heat Pump

         defrosting performance, the outdoor coil could be changed to horizontally installed,
         from Fig. 5.14A to B. With this method, the total area of remaining water could be
         enlarged to 500 mm   590 mm (Side C), or 11.36 times the previous area, as shown
         in Fig. 5.15C–D. Therefore, to quantitatively study the negative effects of surface ten-
         sion, in this paper, an experimental study on defrosting performance for an ASHP unit
         with a horizontal multicircuit outdoor coil was carried out. First, a detailed description
         of the specially built ASHP unit is presented. This is followed by reporting the exper-
         imental procedures and conditions. After the experimental cases and their results are
         detailed, a discussion and energy analysis are reported. Finally, a conclusion is given.




         5.3.1 Experimental cases
         5.3.1.1 Experimental setup, procedures, and conditions
         In this section, the experimental setup was totally the same as that previously used.
         So, it is briefly introduced here. The experimental ASHP unit was modified from a
         commercially available 6.5 kW heating-capacity variable speed ASHP unit. It was
         installed in an existing environmental chamber. In the chamber, there are a simulated
         indoor heated space and a simulated outdoor frosting space, with the same size of
         3.8 m (L)   3.8 m (W)   2.8 m (H). The experimental ASHP unit was a split-type
         one consisting of a swing-type compressor, an accumulator, a four-way valve, an
         EEV, an indoor coil, and an outdoor coil. To control the indoor and outdoor spaces
         to meet the experimental conditions, a separate DX A/C system and two suits of sen-
         sible and latent LGUs were used in the environmental chamber. Finally, frosting envi-
         ronment in the outdoor space could be reached by running the experimental ASHP unit
         and LGUs together while an indoor heated environment by the experimental ASHP
         unit and the existing A/C system. Detailed information about the experimental setup,
         such as the measuring parameters, sensor locations, etc., can be found in the previous
         section.
            Moreover, the experimental procedures and conditions in this section are also
         totally the same as the previous section. To keep the compressor safe, it as always
         switched off before defrosting was started. About 1 min after the shutdown of the
         compressor, the four-way valve was switched to defrosting mode. After about 4 s,
         the compressor was then powered on again manually. Until now, a defrosting opera-
         tion was started in the experiment. The defrosting operation was also manually termi-
         nated when the tube surface temperature at the exits of the three refrigerant circuits in
         the outdoor coil reached 24°C.
            Prior to defrosting, the experimental ASHP unit was operated in the heating
         (frosting) mode for 60 min, at an outdoor frosting ambient temperature of
         0.5   0.2°C (dry-bulb temperature) and 90   3% relative humidity. During heating
         (frosting), the air temperature inside the heated indoor space was maintained at
         20   0.5°C. To supply enough energy for defrosting and keep the ASHP unit work-
         ing safely, the indoor air fan during defrosting remained operational at a lower
         speed. Fig. 5.16 shows the fluctuation of the measured face velocity of the outdoor
         coil during a heating (frosting) operation.
   140   141   142   143   144   145   146   147   148   149   150