Page 143 - Defrosting for Air Source Heat Pump
P. 143

136                                         Defrosting for Air Source Heat Pump

         5.3   Effect of surface tension on uneven defrosting


         Among these exploratory experimental studies on improving system defrosting per-
         formance for ASHP units with vertical multicircuit outdoor coils, the phenomenon
         that different circuits terminate their defrosting processes at different times was found
         and reported. For example, Qu et al. [12] and O’Neal et al. [22] both investigated the
         transient defrosting performances of ASHP units, each with a vertical four-circuit out-
         door coil. It was reported that when a defrosting process was terminated, the surface
         temperature at the exit of the lowest circuit was much lower than that at the exit of the
         highest circuit. In the study by Wang et al. [19], it was also shown that for a vertical
         seven-circuit outdoor coil, at 6 min into defrosting, the surfaces of the lower refrig-
         erant circuits, which accounted for almost one-fourth of the entire coil surface area,
         were still covered by frost while those of the up-circuits were already free of frost.
         Thereafter, to qualitatively and quantitatively study the effects of the melted frost
         downward flowing over the surface of the outdoor coil due to gravity, a series of
         experimental and modeling studies were carried out in an ASHP unit having a vertical
         multicircuit outdoor coil [11, 18, 19]. Finally, it was demonstrated that downward
         flowing of the melted frost due to gravity from the up-circuits would adversely affect
         the defrosting performance of the down-circuits during an RCD operation, thus
         prolonging the defrosting operation and negatively impacting the indoor thermal com-
         fort and energy efficiency of the ASHP unit [20].
            While the outcomes from these studies [11, 18] demonstrated the effectiveness of
         locally draining away the melted frost from a vertical multicircuit outdoor coil with
         water-collecting trays installed between circuits, for an ASHP unit, however, there
         is always some melted frost remaining on the downside surface of each circuit due
         to surface tension. As shown in Fig. 5.14, for a fixed surface area multicircuit outdoor
         coil, the maximum flow path of melted frost oneach circuit would decrease as its circuit
         number increases, from 2H in Fig. 5.14A, A two-circuit outdoor coil, to 4H/3 in
         Fig. 5.14B, A three-circuit outdoor coil, and then to only H in Fig. 5.14C, A four-circuit
         outdoor coil. The energy consumption on heating the cold melted frost downward

                                             Area of remained water
                 Maximum flow path
                                                              H     Circuit 1
                                      4H/3  Circuit 1            A
               2H   Circuit 1                  A
                                                               H   Circuit 2
                       A                                         A
                             4H+h              A    4H+2h       H  A  Circuit 3  4H+3h
           h                           4H/3  Circuit 2
                2H  Circuit 2
                                       4H/3  Circuit 3           H  Circuit 4
                       A                       A                  A
                2H   2A                4H/3   3A                 H    4A
          (A)                       (B)                    (C)
         Fig. 5.14 Maximum flow path of melted frost and total area of remaining water in multicircuit
         outdoor coil. (A) Two-circuit outdoor coil. (B) Three-circuit outdoor coil. (C) Four-circuit
         outdoor coil.
   138   139   140   141   142   143   144   145   146   147   148