Page 147 - Defrosting for Air Source Heat Pump
P. 147

140                                         Defrosting for Air Source Heat Pump


                            Fin                           Fin

                           Vaporizing due to             Vaporizing due to
                           heating from fins             heating from fins

                             Droplets                      Droplets

                        Freely flowing                Clear the water
                        due to gravity                manually
                 (A)                         (B)

         Fig. 5.17 Mass transfer of the retained melted frost during defrosting in the two cases. (A) Case
         1. (B) Case 2.


          Table 5.8 Experimental conditions and relative results in the two cases
          Item   Parameter           Case 1              Case 2

          1      The surface tension of  Kept            Destroyed
                 remaining water
          2      Defrosting duration  186 s              167 s
          3      Total mass of frost  958 g              916 g
                 accumulated
          4      Total mass of melted  948 g             909 g
                 frost collected
          5      Mass of the retained  566 g             42 g
                 water collected
          6      Shown in            Figs. 5.17–5.20, 5.22;  Figs. 5.17, 5.18, 5.21,
                                     Tables 5.9 and 5.10  5.23; Tables 5.9 and 5.10




         5.3.2 Results and analysis
         Four photographs illustrating the airside surface conditions of the outdoor coil at the
         start and end of defrosting in the two cases are shown in Fig. 5.18. As shown in
         Fig. 5.18A1 and B1, it is visually the same and even for the frost accumulated on
         the surface of the outdoor coil in the two cases, which met the requirements previously
         described in Section 5.3.1. As listed in Table 5.8, the frost accumulations were calcu-
         lated at 958 g in Case 1 and 916 g in Case 2, respectively. Their difference was 42 g, or
         about 4.38%, which was small and acceptable in this section. Meanwhile, as predicted,
         a lot of residual water was retained over the outdoor coil downside surface when the
         defrosting operation terminated. As shown in Fig. 5.18A2 and B2, the melted frost
         retained on the downside surface over the horizontal multicircuit outdoor coil in an
         ASHP unit due to surface tension during RCD can be visually observed. The differ-
         ences on the mass of retained melted frost in the two cases were shown in the white-
         dotted rectangles. It is obvious that the retained water in Case 1 was much more than
   142   143   144   145   146   147   148   149   150   151   152