Page 144 - Defrosting for Air Source Heat Pump
P. 144

Investigation of effect on uneven defrosting performance          137

           flowingalong the flow pathwouldbe reduced, and then the defrosting performance was
           expected to be improved. However, at the same time, the total area of the circuit down-
           side surface, or the total area of the remaining water, would increase exponentially,
           from 2A in Fig. 5.14A, A two-circuit outdoor coil, to 3A in Fig. 5.14B, A three-circuit
           outdoor coil, and then even to 4A in Fig. 5.14C, A four-circuit outdoor coil. The
           remaining water would consume energy [26] and thus adversely affect the system
           defrosting performance. Therefore, it is contradictory for the maximum flow path of
           the melted frost and the total area of the remaining water on improving system
           defrosting performance, when increasing circuit number of a fixed surface area
           evaporator.
              To solve this contradictory problem, the most effective method is to eliminate the
           surface tension on the melted frost, and thus decrease the total area of remaining water.
           Therefore, as a fundamental problem, the surface tension effects on melted frost, and
           thus on the defrosting performance for an ASHP unit having a multicircuit outdoor
           coil, should be quantitatively studied. However, as shown in Fig. 5.15, when an out-
           door coil is vertically installed and without any separations between circuits, the area
           of remaining water is very small, just 44 mm   590 mm (Side B). To enlarge the area
           of remaining water, and thus clearly show the negative effects of surface tension on

                          Side A (Topside)
                                      44 mm                         Side B
                    590 mm
                                                                   (Back side)
                             Circuit 1
                                      Side C (Front side)           Circuit 3
               mm                                500 mm
               500           Circuit 2                         Circuit 2
                                                                       Side C
                                                           Circuit 1
                                                                      (Downside)
                             Circuit 3                           44 mm
                                        Side B     Side A  590 mm
                                       (Downside)  (Front side)
             (A)                          (B)


                                                                 Circuit 3
                44 mm             Side B        500 mm

                        590 mm                              Circuit 2
                                                                     Side C
                                                        Circuit 1
                                                  590 mm
             (C)                          (D)
           Fig. 5.15 Area of remaining water for vertically and horizontally installed three-circuit outdoor
           coil. (A) Vertically installed three-circuit outdoor coil. (B) Horizontally installed three-circuit
           outdoor coil. (C) Area of remained water (Side B). (D) Area of remained water (Side C).
   139   140   141   142   143   144   145   146   147   148   149