Page 213 - Defrosting for Air Source Heat Pump
P. 213

The influence of refrigerant distribution on defrosting           207


            Table 7.4 Experimental conditions of two experimental cases
            Item   Parameter       Case 1                 Case 2

            1      FECs            Higher than 90%        Higher than 90%
            2      RDEVs           Lower than 100%        Nearly at 100%
            3      Trays during    Without                Without
                   frosting
            4      Trays during    Without                Without
                   defrosting
            5      Stop valves’    State 1 (even frosting)  State 1 (even frosting)
                   state during
                   frosting
            6      Stop valves’    State 2 (Fully open)   State 3 (Evenly adjusted)
                   state during
                   defrosting
            7      Conditions      Fig. 7.10D             Fig. 7.10C
                   shown in
            8      RDEV            Fig. 7.1               Fig. 7.2
                   adjustment
                   shown in
            9      Effects of URD  Existence (at all stages of  Inexistence (at any stage of
                                   the defrosting process)  the defrosting process)
            10     Effects of      Existence (only at the third  Existence (only at the third
                   MFDF            stage of the defrosting  stage of the defrosting
                                   process)               process)



           on the three circuits were fully open. Also, for easy reference in this study, the set of
           three stop valves fully open was named State 2. Due to gravity and tube internal resis-
           tance, the refrigerant flowing into each circuit was kept at a fixed RDEV lower than
           100%. On the other hand, in Case 2, a series of trial-and-error manual adjustments of
           the opening degree of the stop valves was conducted. To adjust the refrigerant for even
           flow into each circuit, the tube surface temperature at the exit of each circuit was con-
           sidered to guide the control strategy. Using this method, a suite of suitable degrees was
           obtained and fixed for three refrigerant circuits at the start of an RCD operation.
           Meanwhile, this set of valve opening degrees was named State 3. The refrigerant dis-
           tribution condition could be fixed at an RDEV, nearly at 100%. For the negative
           effects of URD, it only exists at all stages of the defrosting process in Case 1. In
           two cases, the negative effects of MFDF only exist at the third stage of the defrosting
           process. At this stage described in Chapter 4, the frost was melting as well as the
           melted frost flowed away from a circuit.
              In order to obtain the opening degrees of the stop valves at State 3 in two cases
           during defrosting, the valves adjustment work was carried out by operating the ASHP
           unit in defrosting mode without any frost accumulating. With the heat transfer
           between the inside and outside of the tube eliminated, the refrigerant distribution
           could be directly reflected in the curve’s trends of tube surface temperatures at three
   208   209   210   211   212   213   214   215   216   217   218