Page 250 - Defrosting for Air Source Heat Pump
P. 250

Energy transfer during defrosting                                 245

              Fig. 8.16 presents eight photographs showing the airside surface conditions of the
           outdoor coil during defrosting in the two cases. Obviously, there are water-collecting
           trays installed under the circuits. Therefore, the two cases can reflect the defrosting
           conditions in an ASHP unit, with the melted frost locally drained. Fig. 8.16(1A–1D)
           are in Case 1, with two working circuits, and Fig. 8.16(2A–2D) are in Case 2, with three
           working circuits, respectively. As observed from Fig. 8.16(1A and 2A), the surface
           conditions at the start of defrosting for each circuit in the two cases were visually
           the same, which agreed well with the fixed high FEC. It is obvious that the frost accu-
           mulations in the two cases are similar, which also met the 358.5 and 360 g listed in
           Table 8.8. In Case 1, the preheating defrosting stage ended before 60 s into defrosting,
           as shown in Fig. 8.16(1B). As shown, the upside tube and fin started to contact with the
           ambient air. As shown in Fig. 8.16(1C), the melted frost was downward flowing away
           from the circuits at about 100 s into defrosting in Case 1. When the defrosting came to
           120 s, most frost was melted off, as presented in Fig. 8.16(1D). However, at 100 s into
           defrosting in Case 2, the preheating stage had ended, and the tube and fin contacted with
           the ambient air for a long time, as shown in Fig. 8.16(2B). At 130 s into defrosting, there
           was still much frost left, as shown in Fig. 8.16(2C). Most frost was melted off at about
           150 s in Case 2, as presented in Fig. 8.16(2D). Comparing the two last pictures in the
           two cases, it was demonstrated that the defrosting duration in Case 1 would be earlier
           by at least 30 s than that in Case 2.
              Using the previously listed equations, the experimental data of the defrosting heat
           supplies and energy consumptions for the experimental ASHP unit in the two
           cases were calculated and presented in Figs. 8.17–8.25.In Figs. 8.17–8.20 and




























           Fig. 8.16 Airside surface conditions of the outdoor coil during defrosting in two cases. (1A) 0 s
           in Case 1. (1B) 60 s in Case 1. (1C) 100 s in Case 1. (1D) 120 s in Case 1. (2A) 0 s in Case 2. (2B)
           100 s in Case 2. (2C) 130 s in Case 2. (2D) 150 s in Case 2.
   245   246   247   248   249   250   251   252   253   254   255