Page 251 - Defrosting for Air Source Heat Pump
P. 251

246                                         Defrosting for Air Source Heat Pump

         8.25, for their time (horizontal) axis, 0 s is the actual start time for defrosting opera-
         tion. From the experiments, the defrosting durations for Case 1 and Case 2 were
         obtained as 136 and 164 s, respectively. It is also reflected in Fig. 8.18. Therefore,
         in Figs. 8.18–8.21 and 8.25, all the data during defrosting are shown. As to
         Figs. 8.22 and 8.23, the melted frost began to flow down from the water-collecting
         tray to the cylinder at 110 and 125 s for Case 1 and Case 2, respectively. As the
         defrosting terminated, the heat transfer between the melted frost collected and the
         ambient air around the outdoor coil continued. Therefore, the data in the two figures
         showed the results until 140 s for Case 1 and 165 s for Case 2 into the defrosting
         operation.
            Fig. 8.17 shows the mean measured tube surface temperature of all outdoor coil
         circuits in the two cases. Clearly, the two curves reached 24°C at 136 s in Case 1
         and 164 s in Case 2, respectively. That means the time difference of the two defrosting
         durations was 28 s, which met the demonstration given in Fig. 8.16. As seen in
         Fig. 8.17, at 60 s into defrosting in Case 1, the tube surface temperature of Circuit
         2 was at about 0.8°C. That means the preheating stage was just over. The tube surface
         temperature of Circuit 2 in Case 2 was at 16°C at 100 s into defrosting. This met
         Fig. 8.16(1B and 2B). At 100 s in Case 1 and 130 s in Case 2, the temperature values
         were at 8.1°C and 12.5°C, respectively. Therefore, in Fig. 8.16(1C and 2C), it was at
         the status of the melted frost flowing downward along the circuits. When it came to
         120 s in Case 1 and 150 s in Case 2, the temperature values were at 16.1°C and 20.3°C,
         respectively. That means Fig. 8.16(2D) is more close to the defrosting termination
         than that in Fig. 8.16(1D). However, from 0 to 20 s, the temperature in Case 1 was
         always lower than that in Case 2. This might be because of different frost accumula-
         tions, at 358.5 g in Case 1 and 360 g at Case 2, as listed in Table 8.5. After 40 s into
         defrosting, the delay of defrosting due to more frost made the temperature in Case 1
         obviously higher than that in Case 2.
            The average values of the indoor and outdoor coils’ measured metal temperatures
         in the two cases are presented in Fig. 8.18. Obviously, at the start of defrosting, the two
         differences were different, at 18.5°C in Case 1 and 7.6°C in Case 2, respectively. This
         might result from their different frost accumulations at the start of defrosting. How-
         ever, at the termination of defrosting, the temperature differences between the indoor
         and outdoor coils in the two cases were nearly the same, at 33.1°C in Case 1, and 32.2°
         C in Case 2. This also confirmed that this comparative study was meaningful. From 0
         to 60 s into defrosting, the two outdoor coil temperatures were nearly kept the same.
         As shown in Fig. 8.18, there is a parallelogram. This is because after 100 s into
         defrosting in Case 1 and 132 s in Case 2, their rates of temperature increase were
         nearly the same. Therefore, the difference of temperature increasing rates came out
         at the melted frost downward flowing stage as described in Chapter 4. It is the melted
         frost effects that make the temperature increasing rate in Case 2 lower.
            The measured air temperature differences between the inlet and outlet of the indoor
         coil in the two cases are presented in Fig. 8.19. As seen, their trends are similar. There-
         fore, during defrosting, the processes of thermal energy taken from the indoor air were
         nearly the same. At 135 and 140 s into defrosting in the two cases, the curves reached
         their peaks at the values of 13.8°C and 14.0°C. The curve of Case 2 was also few later
   246   247   248   249   250   251   252   253   254   255   256