Page 253 - Defrosting for Air Source Heat Pump
P. 253

248                                         Defrosting for Air Source Heat Pump


                     16
                                                      o
                                                   14.0 C
                     14         Case 1          13.8 C
                    Measured air temperature difference ( o C)  10 8 6 4
                                                   o
                     12
                                Case 2







                      2

                      0
                        0   20  40   60  80  100  135 s  140  140 s  180  200
                                                 120
                                                          160
                                           Time (s)
         Fig. 8.19 Measured air temperature differences between the inlet and outlet of the indoor coil.



























         Fig. 8.20 Energy input to the compressor during defrosting in the two cases.


         The data in Case 2 were always lower than those in Case 1. It looks contradictory
         because the total frost that accumulated in Case 1 was much more than that in Case
         2, as listed in Table 8.8. However, it mainly resulted from the higher frost density in
         Case 1, which increased the energy taken rate during defrosting. In addition, the
         energy input to the compressor was kept small, at lower 3.0 kJ, at 0–86 s in Case 1
         and 0–100 s in Case 2. It is demonstrated that at the start of defrosting, little energy
   248   249   250   251   252   253   254   255   256   257   258