Page 252 - Defrosting for Air Source Heat Pump
P. 252

Energy transfer during defrosting                                 247




















                                           Fig.8.16(2B)





           Fig. 8.17 Mean measured tube surface temperatures of all outdoor coil circuits.


                       40
                                Indoor coil (Case 1)
                       35       Outdoor coil (Case 1)     32 s
                                Indoor coil (Case 2)
                     Measured mean metal temperature ( o C)  25  18.5 C   flowing stage  33.1 C  32.2 C
                       30
                                Outdoor coil (Case 2)
                                                   32 s
                       20

                       15
                                            Melted frost
                                            downwards
                       10
                        5
                            7.6 C
                        0
                                     60 s          132 s
                       –5
                           0    25   50   75   100  125   150  175  200
                                             Time (s)

           Fig. 8.18 Measured mean metal temperatures of the indoor and outdoor coils in the two cases.


           than that of Case 1. This reflects that the energy taken process in Case 1 was much
           quicker than that in Case 2. Fig. 8.20 shows the energy input to the compressor during
           defrosting in the two cases. The two curves’ trends are similar, with the curve of Case
           1 increasing much quicker after 80 s into defrosting. At the end of defrosting, they
           reached their peak values at 3.72 kJ in Case 1 and 3.66 kJ in Case 2, respectively.
   247   248   249   250   251   252   253   254   255   256   257