Page 272 - Defrosting for Air Source Heat Pump
P. 272

266                                         Defrosting for Air Source Heat Pump



























         Fig. 9.7 The fluctuation of melted frost temperature collected in Cylinder D in the five
         experimental cases.



























         Fig. 9.8 The fluctuation of refrigerant volumetric flow rate at defrosting mode in the five
         experimental cases.

         shows the fluctuation of refrigerant volumetric flow rate at defrosting mode in the five
         experimental cases. Obviously, these curves reached different peaks at different times
         due to different frost accumulations. It is 1.39 L/min at 145 s in Case 1, 1.40 L/min at
         155 s in Case 2, 1.35 L/min at 160 s in Case 3, 1.34 L/min at 170 s in Case 4, and
         1.32 L/min at 175 s in Case 5, respectively. The five curves, the same as the previous