Page 537 - Design of Reinforced Masonry Structures
P. 537

SHEAR WALLS                       7.99

         1. Factored axial load stress ≤ 0.2  ′ f
                                  m
         2. Slenderness ratio (h/t ratio) ≤30
         3. Minimum nominal thickness ≥6 in. (Not a code requirement, but a practical minimum.)
           It is, therefore, only logical that a limit to  h/t  = 30 be maintained for shear walls.
         Expressions for axial loads on compression elements were derived in Chap. 5. It was shown
         that for rectangular sections,

                                      r =  t                  (5.16 repeated)
                                          12
         so that                      t =  r 12                      (7.96)
         Therefore, the condition h/t = 30 can be expressed in terms of h/r ratio as follows:
                                    h   h
                                     =     = 30
                                    t  r 12
                                 h
         so that                   = 30 12  = 103 923                (7.97)
                                             .
                                 r
           Equation (7.97) can be treated as the upper limit for h/r ratio for a shear wall. Accordingly,
         the nominal axial strength of a shear wall can be expressed, based on MSCJC-08 Section
         3.3.4.1, Eq. (3.17) [see Chap. 5, Eq. (5.11)]:

                        P = 080 080  f ′( A −  A +  f A ⎜ ] ⎛ 70 r ⎞ ⎟  2
                             .[ .
                                           )
                         n         m  n   s   y  s  ⎝  h ⎠
                                                 ⎛  70  ⎞  2
                          = 08 . 000 80[.  ( ′ f  A  − A  ) + f A  ] ⎜  ⎟
                                   m  n   s   y  s  ⎝ 103 923 ⎠
                                                    .
                          =  03 . 663 0 80[.  ( ′ f  A  − A  ) + f A  ]      (7.98)
                                    m  n   s  y  s
         Equation (7.98) can be treated as the limiting value of nominal axial capacity of reinforced
         masonry walls.
           The strength factor f to be used for axial loads, axial loads with flexure, or flexure, is 0.9
         (MSJC-08 Section 3.1.4.1). Example 7.17 presents analysis of a shear wall under flexure.

           Example 7.17
             Calculate the flexural capacity of the 8-in. (nominal) shear wall having cross sec-
           tion as shown in Fig. E7.17A. The wall constructed from 8 × 8 × 16 (nominal) concrete

           masonary units (CMUs) measures 18 ft. 8 in. end-to-end and reinforced with 10 No
           6 Grade 60 bars spaced at 24 in. on centers. The compressive strength of masonry is
                   2
           2000 lb/in. .
                                                                    Tension
           Compression                  M
           face   1    2     3    4     5     6    7     8    9    10  face
             7.625''
                 4''                    10#6 @ 24''                  4''
                                          18'–8''
           FIGURE E7.17A  Reinforced masonry shear wall subjected to flexure.
   532   533   534   535   536   537   538   539   540   541   542