Page 302 - Failure Analysis Case Studies II
P. 302

287




















                                                                Pump
                                        Fig. 4. Design fault 1-pumping  water through the expansion tank.



                       2.1.  Oxygen pick-up
                         There are a number of ways in which the water can pick up oxygen. Obviously, some air will get
                       in when the circuit is drained down (e.g. for repairs, or when there is a risk of freezing) and then
                       refilled. A  limited amount of fresh water is taken into the system to compensate for evaporation
                       from thc cxpansion tank  or losses due to leaks, and this, too, is a source of oxygen. But a major
                       intake of oxygen is usually caused by design faults in the pipework.
                         A typical fault is shown in Fig. 4 [4]. If the flow resistance of the radiator circuit is large compared
                       to that of the boiler, then, depending on the location of the pump, water can be forced up the vent
                       and discharged into the expansion tank. A particularly bad location for the pump is shown in Fig.
                       &in  the return line between the cold feed and the boiler. It is easy to see that, when a large pressure
                       drop is needed to get the water to flow around the radiator circuit, then the water will tend to take
                       the easier route,  and there will be a circulation loop between the boiler and the expansion tank.
                       Naturally, as the water pours out of the vent it continually picks up air. This “pumping over” would
                       not have happened if the pump had  been positioned to the left  of  the cold feed instead of to the
                       right. Figure 1 shows the standard position for the pump in a modern installation-in  the flow line
                       after the vent. When the pump is put in this position pumping over cannot occur.
                         Figure 5 shows another fault-when  air is drawn in down the vent pipe [4]. In order to pull water
                       through the boiler the pump must generate a low pressure in the flow line from the boiler. This low
                       pressure depresses the head of water in the vent pipe. If the expansion tank is not high enough, the
                       surface of the water in the vent pipe will be pulled down to the level of the flow line, and bubbles of
                       air will be swept into the circuit. Oxygen concentrations of  w 5 ppm have been found in systems




                                                             Air







                                          Radiator
                                           circuit

                                           Fig. 5.  Design fault 24rawing air in through the vent.
   297   298   299   300   301   302   303   304   305   306   307