Page 303 - Failure Analysis Case Studies II
P. 303

288












                                                    Vented
                                                    system
                                    ,


                                    0            50           IO0
                                                T ("C)
                     tig. 6.  Rate of corrosion of mild steel in aerated mains water as a function of temperature.

           suffering from this defect [4]. To avoid air intake, the static head h must be greater than the flow
           resistance of the boiler by a suitable safety margin; a typical value for h is 1.5m.
             In  order  to  guarantee  that  oxygen  is  excluded  from  the  system,  the  trend  in  most  modern
           installations  has  been  to replace the  traditional  open  expansion  tank  with  a  sealed air cushion
           expansion tank. The system water expands into a polymeric bag which is contained in an outer tank
           of pressurized air.

           2.2.  Corrosion rates
             When the water is saturated with oxygen, the steel will corrode rapidly. The rate of corrosion is
           controlled by the oxygen-reduction reaction, which is in turn controlled by the rate at which oxygen
           diffuses through  the water  to the surface of the steel. Because diffusion is a thermally-activated
           process, the rate of diffusion will increase exponentially with temperature. So also will the corrosion
           rate, as shown by the rising curve in Fig. 6. As one approaches 80°C,  the curve divides into two
           branches [3, 51. If the system is pressurized (so none of the dissolved oxygen can escape), the curve
           carries on upwards. But if  the system is vented (as most central heating systems are), the oxygen
           can come out of solution as the water warms up. As the oxygen concentration falls below 3 mg I-',
           the oxygen-reduction reaction slows considerably, and at 100 "C the steel is corroding no faster than
           it would have done in aerated water at 25 'C.

           2.3.  Diagnosis
             It is relatively easy to find out whether excessive oxygen has been getting into a heating system.
           When oxygen is plentiful, the iron corrodes rapidly at a relatively high potential. The reaction takes
           place in the Fe203 field of the Pourbaix diagram (see Fig. 3),  and a red sludge of hydrated ferric
           oxide collects at the bottom of the radiators. When oxygen is scarce, the iron corrodes slowly at a
           relatively low potential. The reaction generates ferrous ions, and a thin black coating of hydrated
           magnetite (magnetic iron oxide) forms instead. Both oxides are 5 times as dense as water: although
           oxide particles can be carried around with the circulating water, most of the sludge remains in the
           radiators. Contrary to the view commonly held by many heating engineers, oxide sludge cannot be
           removed by flushing water through the radiators (although it can be removed by circulating a warm
           solution of inhibited phosphoric acid through the system).


                         3.  OXYGEN  REDUCTION-SOME     COMPLICATIONS

             There are several things which can make steel corrode faster in the presence of oxygen. These are
           summarized as follows.
   298   299   300   301   302   303   304   305   306   307   308