Page 310 - Flexible Robotics in Medicine
P. 310

300 Chapter 13

            length, thus allowing it to carry out an equivalent function more effectively as per design
            acceptance criterion 10. Furthermore, this modification in design does not compromise
            design acceptance criterion 2, as the segments still fit securely within each other, kept in
            place by the nylon threads, which run the entire length of the flexible tip.
            The dimensions for the main conduit module and relevant illustrations are shown in
            Fig. 13.12.



            13.4.3 Connector

            The evolution of the connector module is shown in Fig. 13.13. The connector module is
            not as crucial to the flexible vase-spine modular design, but some subtle differences can
            be observed, as the design progresses forward: (1) the design similarly adopts a less
            angular and more rounded conformation, (2) the openings at the top and bottom ends
            “narrow,” and (3) the chamfers at the top and bottom ends smoothen and become more
            pronounced.

            The rounded conformation of the design was adopted in accordance with design acceptance
            criterion 1 (Section 13.4.1) as the main conduit module (Section 13.4.2). As for the change
            in geometry of the design, it was designed as such to fulfill design acceptance criteria 2, 3,
            and 10 (Section 13.4.1), as mentioned in Section 13.4.2.

            As we progressed with the design of the connector module, the opening of the connector
            module grew narrower to parallel the decrease in the diameter of the distal ends of the main
            conduit module to prevent compromise of design acceptance criterion 2, as the segments
            must fit securely within each other.
            As for the smoother and more pronounced chamfers at the top and bottom ends of the
            connector module, it was observed that a more pronounced chamfer also contributed to
            a greater bending angle between segments of the flexible tip, albeit to a lesser degree
            than the main conduit module. This allowed BEE to achieve its intended observation
            field as in design acceptance criterion 3 with further reduction in the length of the
            flexible tip, thereby allowing it to carry out an equivalent function as per design
            acceptance criterion 10. The dimensions for the main conduit module and relevant
            illustrations are shown in Fig. 13.14.







                                                Figure 13.13
                        Connector evolution (from left to right: Prototype 1.0 Prototype 7.0).
   305   306   307   308   309   310   311   312   313   314   315