Page 489 - Subyek Teknik Mesin - Forsthoffers Best Practice Handbook for Rotating Machinery by William E Forsthoffer
P. 489

Be st Practice 7 .36          Lube, Seal and Control Oil System Best Practices












































       Fig 7.36.7   Dedicated 6P control buffer

       Gas seal applications                                reactors, usually cannot tolerate any large amounts of oil in the
                                                            system. Oil carryover can necessitate an entire unit shutdown
       Refer to Figure 7.36.6. This application ensures that the gas in  and extensive cleaning time. Care must be taken to select
       contact with the seal will be buffer gas. In this example, the  a system that precludes this possibility.
       buffer gas originates from the compressor discharge, but must  Buffer gas reference
       be conditioned and filtered (ten microns) to meet gas seal re-  Systems incorporating buffer gas use the buffer gas supply as
       quirements to preclude the possibility of gas seal passage foul-  a reference for differential pressure control of the liquid seals.
       ing. In this case, oil ingestion is not a problem since a gas seal is  The valve selection of all buffer gas systems must be carefully
       used. Also, the differential pressure does not need to be regu-  made to prevent unstable valve operation. Valve hunting will
       lated since the seal can withstand high differential pressures.
                                                            cause proportional swings of the seal differential reference
                                                            pressure. High swings, i.e., increasing pressure will result in
                                                            decreasing seal oil to reference gas differential pressure which
       Multiple control valves, vented traps
                                                            can lead to unit shutdowns.
       Figure 7.36.7 shows a design which utilizes a dedicated differ-
       ential pressure control valve to each seal. This design is utilized  Single buffer gas valve, vented traps
       to ensure proper pressure differential (buffer gas to process gas)
       at each seal. In this application, traps are vented which ensures  Figure 7.36.8 shows this system.
       a flow from the buffer gas system gas labyrinths down through
       the traps. Proper sizing of the vent orifices can eliminate the  Oil ingestion prevention systems
       possibility of oil ingestion.
                                                            In the case that oil ingestion is prohibited, the following systems
                                                            can prevent the possibility of oil carryover into the compressor if
       System reliability factors
                                                            properly designed and maintained.
       Oil ingestion                                          By properly sizing orifices in the vents of each contaminated
       As mentioned above, oil ingestion can be a serious problem.  seal oil drainer, a flow will be initiated to positively ensure
       Processes that require dry gas, utilize exchangers, or incorporate  all seal oil leakage is brought to the traps. Remember that in the

           460
   484   485   486   487   488   489   490   491   492   493   494