Page 126 - Handbook of Structural Steel Connection Design and Details
P. 126

Design of Connections for Axial, Moment, and Shear Forces

                           Design of Connections for Axial, Moment, and Shear Forces  111

                    for erection, which is much more stringent than the OSHA load, is a
                    1-kip working load, applied at the top of the column in any horizontal
                    direction. If the column is, say, 40 ft high, this 1-kip force at a lever arm
                    of 40 ft will cause a significant couple at the base plate and anchor
                    bolts. The base plate, anchor bolts, and column-to-base plate weld should
                    be checked for this construction load condition. The paper by Murray
                    (1983) gives some yield-line methods that can be used for doing this.
                    Figure 2.26 shows four anchor rods. This is an OSHA erection require-
                    ment for all columns except minor posts.

                    2.2.5 Splices—columns and truss chords
                    Section J1.4 of the AISC Specification (2005) says that finished-to-bear
                    compression splices in columns need be designed only to hold the parts
                    “securely in place.” For this reason, the AISC provides a series of “standard”
                    column splices in the AISC Manual of Steel Construction. These splices are
                    nominal in the sense that they are designed for no particular loads. Section
                    J1.4 also requires that splices in trusses be designed for at least 50% of the
                    design load (required compression strength), or for the moment and shear
                    resulting from a transverse load equal to 2% of the required compressive
                    strength of the member, whichever is less severe. The difference between
                    columns and “other compression members,” such as compression chords of
                    trusses, is that for columns, splices are usually near lateral support points,
                    such as floors, whereas trusses can have their splices at mid-panel points
                    where there is no lateral support. Either the 50% requirement or the 2%
                    requirement can be used to address this situation.

                      Column splices. Figure 2.27 shows a standard AISC column splice for
                    a W14   99 to a W14   109. If the column load remains compression,
                    the strong-axis column shear can be carried by friction. The coefficient
                    of static friction of steel to steel is on the order of 0.5 to 0.7, so quite high
                    shears can be carried by friction. Suppose the compression load on this
                    column is 700 kips. How much major axis bending moment can this
                    splice carry? Even though these splices are nominal, they can carry
                    quite significant bending moment. The flange area of the W14   99 is
                                               2
                    A   0.780   14.565   11.4 in . Thus, the compression load per flange is
                      f
                    700   11.4/29.1   274 kips. In order for a bending moment to cause a
                    tension in the column flange, this load of 274 kips must first be unloaded.
                    Assuming that the flange force acts at the flange centroid, the moment
                    in the column can be represented as:
                                 M   T(d   t )   T(14.16   0.780)   13.38T
                                            f
                    If T   274 kips, one flange will be unloaded, and M   13.38   274
                    3666 kips-in   306 kips-ft. The design strength in bending for this
                    column (assuming sufficient lateral support) is  M   647 kips-ft. Thus,
                                                                  p
                    because of the compression load, the nominal AISC splice, while still
                    seeing no load, can carry almost 50% of the column’s bending capacity.


                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.accessengineeringlibrary.com)
                             Copyright © 2009 The McGraw-Hill Companies. All rights reserved.
                              Any use is subject to the Terms of Use as given at the website.
   121   122   123   124   125   126   127   128   129   130   131