Page 31 - Industrial Power Engineering and Applications Handbook
P. 31

1/12  Industrial Power Engineering and Applications Handbook
        thereby increasing I, a proportion of which will depend   by the lower voltage, the stator must draw a higher current
        upon the magnitude of  voltage.                from the supply to compensate for the higher losses at
                                                       lower voltages. Since
        Important note on starting torque, T,,
        It is important to note that at voltages lower than rated
        the degree of saturation of  the magnetic field is affected
        as in equations (1.1) and (1.5). There will also be a further   if the supply voltage falls to 85%, the stator current for
        drop in the supply voltage at the time of start-up. The net   the same load should increase by
        effect of such factors is to further influence the starting   I:  = IJ0.85,i.e.  by roughly  18% and if the voltage
        performance of the motor. See also IEC 60034-12. For   increases by  15%,  the stator current should decrease to
        risk-free duties and large motors, HT motors particularly,   IJl.15 or 87% of Ir, i.e. areduction of 13%. These would
        which have a comparatively lower starting torque, it would   be the values when the core losses are ignored. But the
        be appropriate to allow margins for such factors during   core losses will also vary with the voltage as discussed
        start-up. Table 1 .5, based on the data provided by a leading   below. Moreover, at a higher voltage, the p.f. will also
        manufacturer, shows such likely factors at various voltages.   become poorer and the motor will draw a higher current
        The square of these must be applied to derive the more   to account for this. All such factors, therefore, must be
        realistic operating starting torques at lower voltages than   considered  when making a selection of the rating  of  a
        rated, rather than applying only the square of the applied   motor, particularly for critical applications.
        voltage. Such a precaution, however, may not be necessary
        for normal-duty and smaller motors.            (iv) Core and load losses
                                                       A current-canying conductor produces two types of losses,
        Example 1.3                                    i.e.
        Consider a 750 kW, 4-pole  motor, having a rated starting
        torque  Td as  125% of the  rated and starting current /* as   1  Resistive losses = 12R and
        600% of the rated. At  80% of the rated voltage the starting   2  Core losses or magnetizing losses, which comprise
        torque T. will reduce to
                                                            Eddy current losses and
         Tst at 80% V, = 125 x 0.745'                       Hysteresis losses
                  = 69% of rated (and not 125 x 0.82 or
                    80% of rated)                      Magnetizing losses, however, as the name implies, are a
                                                       phenomenon in electromagnetic circuits only. They are
        (ii)  Starting current                         absent  in  a non-magnetic  circuit.  A  motor  is  made  of
        In the same context, the starting current will also decrease   steel laminates  and the housing  is  also of  steel, hence
        linearly according to this factor and not according to the   these  losses.  Some  manufacturers,  however,  use
        supply voltage. In the above example, the starting current   aluminium die-cast stator frames in smaller sizes, where
        Ist at 80% of the rated voltage will therefore reduce to   such losses will be less (the bulk of the losses being in
                                                       the laminations),
        ISt = 600 x 0.745                                Since the resistive loss would vary in a square proportion
           = 447%  (and  not  600 x 0.8  or  480%)  of  the  rated   of the current, the motor will overheat on lower voltages
             current.                                  (drawing higher currents). At higher voltages, while the
                                                       stator current may decrease, the core losses will be higher.
         (iii) Loud current                              To understand magnetizing losses, we must first identify
         In addition  to the  increased  stator current necessitated   the  difference  between  the  two  types  of  losses.  Both
                                                       represent losses as a function of the electric field, generated
                                                       by  the current-carrying  conductors. A current-carrying
         Table 1.5  Multiplying factor for starting torque at lower   conductor generates an electric field in the space around
         voltages                                      it  such that I=  4.  The higher  the current through  the
                                                       conductor,  the  stronger  will  be  the  field in the  space.
         System voltage as   Approx. multiplying factor   Some of the current will penetrate through the conductor
           % of  rated         (apply square of this)
                                                       itself, because of the skin effect and the rest will occupy
                        For 2- and 4-pole   For 6- and &pole   the space. In an electric motor it will penetrate through
                            motors          motors     the stator and the rotor core laminations and the housing  -
            IO0             1 .o            1 .O       of  the motor and cause losses in the following way:
            95              0.93            0.925      1  Resistive losses within the current-carrying conductors,
            90              0.87            0.86          i.e. within the electrical circuit itself, caused by the
            85              0.805           0.79
            80              0.745           0.73          leakage  flux  (Figure  2.6), as  a  result  of  the  deep
            75              0.68            0.665         conductor skin effect. This effect increases conductor
            70              0.625           0.605         resistance and hence the losses. For more details refer
            60              0.5 1           0.49          to Section 28.7.
            50              0.40            0.38       2  Losses  as  caused  by  its  penetration  through  the
                                                          magnetic structures (core) and components existing
         Source  Siemens Catalogue M20-1980               in the vicinity. These losses can be expressed by:
   26   27   28   29   30   31   32   33   34   35   36