Page 372 - Industrial Power Engineering and Applications Handbook
P. 372

Switchgear  and controlgear  assemblies  13/347
                                                       - - - - - &$ F! %
                     z,
       Impedance   -  Zl    -31      z2      -32       z3    -   zt3  -   4   zt4   z5   -
          Section
                        ,  ,                                                        LT loads
                   I    I I


                   11  kV  to
                   11 kV to
                    24 kV
                           yard                                            @
                           yard
                                  220
                                     or
                               132, 220 or                                              0
                               132,
                                                                  11, 6.6
                                   kV
                                400 kV           33 kV            or 3.3 kV     400/440 V
                                400
                    ---v----
                     Generating station   Primary   Receiving   Secondary   Main receiving   L.T.  distribution
                                   transmission   station   transmission   and H.T. distribution
                                                                     station
                               @Generator.            @ Secondary transmission line
                               @Isolated  phase       @ H.T. distribution transformer
                                 bus system
                                                      @ H.T. distribution network
                               @ EHV generator
                                 transformer          @ L.T. distribution transformer
                               @ EHV transmission line
                                                      @)  L.T. distribution network
                               @ H.T. secondary
                                 transmission transformer
                                     (i)  Fault at ‘A’ is calculated by impedance Ztl
                                    (ii)  Fault at ‘B is calculated by impedance 213
                                    (iii)  Fault at ‘C’ is calculated by impedance Zt4
       Note  The actual fault at any point will be much lower than calculated with the above impedances Ztl, &,Zt3  and 214 because other impedances
       from the source of  supply (Transformers in the above case) up to the point of fault, are not considered while designing a system.
       Figure 13.15  Typical layout of a typical transmission and distribution network and significance of circuit impedances at various points


       maximum loading of a line and the maximum number of   contain the fault level within the prescribed limits. For
       feeding lines that may be connected to a common grid,   current limiting reactors refer to Chapter 27.
       to limit the fault level of the system within the desirable   With the availability of more advanced interrupters in
       limit. Some typical values are noted below:    future, it will be possible to upgrade the present guidelines
                                                      and  permit  connections  of  more  feeding  lines  on  an
       Nominal system   Limiting fault   No. of additional   existing grid without having to resort to a series reactor.
       voltage         level        feeding lines       Below, we analyse the likely fault levels of a system
                                                      under different circuits and fault conditions for an easy
       765 kV          2500 MVA      Nil              understanding of the subject. It is a prerequisite to decide
       400 kV          1000 MVA      5                the level of fault, to select and design the right type of
       220 kV           320 MVA      3                equipment, devices and components and the protective
       132 kV           150 MVA      2                scheme for a particular network.
                                                        A power circuit is basically an R-L circuit. In the event
       For more details refer to Section 24.8. It is possible that   of  a  fault,  the  system  voltage  (V, sin  4) may  occur
       in the course of  time more generating  stations may be   somewhere between  V = 0 and  V = V,  on its  voltage
       installed  to  meet  the  rising  demand  for power.  Their   wave. This will cause a shift in the zero axis of the fault
       feeding lines too will be added to the existing grid to   current, Zsc,  and give rise to a d.c. component. The fault
       augment its capacity. This would also enhance the fault   current will generally assume an asymmetrical waveform
       level of the existing system. To ensure that the prescribed   as illustrated in Figure  13.27.
       fault level is not exceeded, a detailed network analysis   The magnitudes of symmetrical and non-symmetrical
       may be carried out to determine the minimum possible   fault currents,  under  different  conditions  of  fault  and
       impedance of the grid, at various vulnerable locations,   configurations of faulty circuits, can be determined from
       to establish the likely revised fault level. If it is felt that   Table  13.5, where  Z1 = Positive  phase  sequence
       it may exceed the prescribed limit, current-limiting series   impedance, measured under symmetrical load conditions.
       reactors  may  be provided  at  suitable  locations  to  yet   The following values may be considered:
   367   368   369   370   371   372   373   374   375   376   377