Page 369 - Industrial Power Engineering and Applications Handbook
P. 369

13/344  Industrial Power Engineering and Applications  Handbook
        Table 13.1  Rated voltages and frequencies for metal enclosed   List I
        bus systems also applicable for switchgear assemblies   1  When  the  system  is  not  directly  connected  to  an
                                                         overhead  line,  such  as  when  connected  through  a
          ~~              ~      ~
        Series  I             Series II                  transformer.
                                                       2  When the neutral of the system is grounded solidly or
        Nominal   Rated maximum  Nominal   Rated  muximum
        system voltage  system voltage  system voltage  system voltage   through a small impedance (Section 20.4).
                                                       3  When the system is provided with a surge protection.
                              (ANSI C37-20C)
        kV        kV         kV         kV
         0.415*    0.44        0.48      0.508         List I1 or List 111
         0.6*      0.66        0.60      n.m           1  When the system is connected to an overhead line.
         3.3       3.6         4.16      4.76          2  When the neutral of the system is not solidly grounded.
         6.6       7.2         7.2       8.25          3  When no surge protection is provided.
        11         12         13.8      15.0           4  When  the  installation  demands  a  high  degree  of
        15         17.5       14.4      15.5             security, such as in a generating station.
        22        24          23.0      25.8
        33        36          34.5      38.0
        44        52          69.0      72.5           Note
        66        72.5         -         -             IS 8084, however, has opted for list I1 for the busbar systems for all
                                                       applications.
        For higher voltages -refer  to Tables 13.2 and  13.3 for series 1 and   Although  the  rated  values  are  based  on experience and  field
        IEC 60694 for series 11.                       data collected, sometimes these values may be exceeded in actual
                                                       operation, due  to  changed  service or  weather  conditions. It  is,
                                                       therefore, recommended to take cognisance of this fact and provide
        Frequency: 50 or 60 Hz   I Frequency: 60 Hz
                                                       a surge protection  to contain the  surge voltages  within  the rated
                                                       values of Tables  13.2 and 13.3. It is recommended  that actual site
        Based on IEC 60694, BS  159 and ANSI C37-2OC.
                                                       tests  be conducted on  similar installations to  ascertain  the likely
        Notes                                          level of voltage surges that may occur during operation. To be on
        Series I:  Based on the current practices adopted by  India, Europe   the safe side, it is recommended for outdoor installations, particularly,
               and several other countries. *These voltages  have now   to  contain  the  severity  of  the  surge  voltages,  with  the  help  of
               been revised  from 0.415 kV to 0.4 kV and from 0.6 kV   surge arresters, within  the  maximum  assigned  impulse  voltages
               to 0.69 kV as in IEC 60038.             (BIL) of  the equipment, considered  in Tables  13.2 and  13.3, less
        Series 11:  Based on the current practices  adopted in the USA and   the protective margins,  for range  I  and range I1  voltage  systems
               Canada.                                 respectively.
        Table 13.2  Standard insulation  (impulse) Levels for Series 1 range  I voltage systems (1 kV <  V,,, 2 245 kV)

                                          Standard  one-minute power frequency   Standard lightning impulse (1.2/50~)
        voltage'  v,,,   system voltage  V,,,   withstand voltage        withstand  voltage phase  to ground**
        kV(c  m.s.)      kV(ctn.s.)       KV*(r.m.s.)                    kV*  (peak)
                                          List  I   List I1   List IIl   List I   List II   List IIl
          3.3             3.6                                            20        40       -
          6.6             7.2                                            40        60       -
         11               12                                             60        75       -
         15               17.5                                           75        95       -
         22              24                                              9s       125       -
         33              36                                              145      I70       -
         44           ~   52                                            250       -         -
         66           ,   72.5                                          325       -         -
        -                100              150      185       -          380       450       -
         110             123              185      230       -          450       550       -
         132          ~   145             230      275       -          550       650       -
         154          1   I70             275      325       -          650       750       -
        220              245              360      39s       460         850      950       1050
        Notes  As in IEC  60071-1 and IEC  60694
        * More than one lightning impulse insulation level is indicative of the extent of exposure of equipment to lightning surges. Correspondingly
        the power frequency withstand  voltage can also he more than one.
        ** Lightning stress between the phases is not more than the lightning stress between a phase and the ground. For more details refer to IEC
        6007 1-1.
        'IEC 60071-1 has specified only  V,,, values.  V,,,,, is indicated  based on the practices  adopted by  various countries.
   364   365   366   367   368   369   370   371   372   373   374