Page 371 - Industrial Power Engineering and Applications Handbook
P. 371

13/346 Industrial Power Engineering and Applications Handbook
         Table 13.4  Conventional values of  diversity factor   Section -   1   2     3      4

         Number of  main outlets   Diversis factor                           630A    630A   800A
          2 to 3            0.8
          4 to 5            0.7
          6 to 9            0.6                                               630A   630A   630A
         IO and above       0.5                                  l/C 4000A
                                                                   ACB
         As in IEC 60439-1                                                    630A   400A   400A

         the rating of a feeder (outlet), as noted above. It is therefore     630A   400A   400A
         recommended that this factor be specified by  the user,
         depending  upon  likely capacity  utilization, to help the
         switchgear  assembly  manufacturer  to  design  a  more   Total connected feeder   2520A   2060A   2230A
         economical busbar  system. In  the  absence of  this,  the   load          681 OA  -
         factors as indicated in Table  13.4 may be applied.   Total connected load

         Example 13.1                                     Diversity factor as per   08   0.8   0.8
         Consider the power distribution system of Figure 13.14, having   Table 13 4
         the following feeder details:                    Maximum loading at   201 6A   1648A   1784A
                                                          any time
         I/C feeder, 4000A                                Recommended rating of   2000A   1600A   1800A
                   1  1 No. 800 A = 800 A                 busbar
         O/G feeders  7 Nos. 630 A = 4410 A and,
                    4 NOS. 400 A = 1600 A
         :.   Total connected feeder  load   = 6810 A         Figure 13.14  Illustration of diversity factor
             and diversity factor for  12 Nos.          the  source  of  supply  to  feed  the  faulty  circuit,  and  is
             feeders as in Table 13.4   = 0.5           represented  in  kVA  or  MVA.  Consider  the  simple
         :.   Maximum loading on the                    transmission  and  distribution  network  of  Figure  23.1,
             incoming feeder or the main                which is redrawn in Figure  13.15 for more clarity. This
             busbars at any time        = 6810 x 0.5    illustrates the impedances of the network at various points,
                                        = 3405 A        and their role in the event of a fault. The impedance of
           Accordingly  we have selected the  rating of the  incoming   a  circuit  is  built  through  the  self-impedances  of  the
         feeder as 4000 A. 4000 A being the next standard rating after   windings of the various machines in the circuit, generators,
         3150A. The  maximum  loading  on  each vertical  section  is   transformers and motors etc., and the impedances of the
         worked out in Figure 13.14. These ratings of vertical busbars   connecting transmission  and distribution  lines  and  the
         are when the arrangement of busbars is to individually feed   associated cables.
         each vertical  row. If one common set of  busbars is feeding   To  increase  the  impedance  of  the  network,  a  series
         more than one vertical section, the rating of  busbars can be   resistor or reactor is sometimes used to contain the fault
         further economized. But one must take cognisance that too   level  of a system within a desirable limit. This may be
         many tapings from one section of the bus may weaken the
         bus system.                                    required to make the selection of the interrupting device
           If two sections are joined together to have a common vertical   easy, and from the available range, without an extra cost
         bus system,  say,  Sections  3  and 4,  then  the  rating of  the   for a new design as well  as an economical  selection of
         common bus will be:                            the interconnecting conductors and cables. Such a situation
                                                        may arise on HV >66 kV or EHV >132. kV transmission
         Total connected load        = 2060 + 2230      networks, when they are being fed by two or more power
                                     = 4290 A
                                                        sources, which may raise the fault level of the system to
         Diversity factor for 8 numbers of  feeders = 0.6   an unacceptable level. The cost of the interrupting device
         :.  Maximum rating          = 4290 x 0.6       for  such  a  fault  level  may  become  disproportionately
                                     = 2574 A           high, and sometimes even pose a problem in availability.
         or say                      = 2500 A             Ground fault current is controlled by a method similar
                                                        to  that  discussed  in  Section  20.4.2.  The  electricity
         as against 1600 A + 1800, i.e. 3400 A, worked out in Figure   authorities of a country generally provide the preferred
         13.14, when both the sections were fed from individual busbars.
                                                        fault  levels,  depending  upon  the  availability  of  the
                                                        interrupting devices. They also suggest the likely genera-
         5 Rated short-time current rating or           tion of  overvoltages in  a faulty circuit and the healthy
         fault level of  a system                       phases  on  a  ground  fault  as  a  result  of  grounding
                                                        conditions, as guidelines to the system designers to design
         To establish the fault level of  a system      a transmission or a distribution network for various voltage
         The fault level of an electrical network is the capacity of   systems. The  guidelines  may  also  recommend  the
   366   367   368   369   370   371   372   373   374   375   376