Page 370 - Industrial Power Engineering and Applications Handbook
P. 370

Switchgear and controlgear assemblies  13/345
      Table 13.3  Standard insulation (impulse) levels for range II  voltage systems (V, > 245 kV)

      Nominal    Highest voltage   Standard one-minute   Standard switching  impulse (250/2500 ps)   Standard lightning
      system     for equipment   power frequency   withstand voltage                 impulse  (1.2bOp)
      voltage    vm           withstand voltage                                      withstand voltage
                                                                                     phase to ground’

      kV(r.m.s.)‘   kV(r.m.s.)   kV(r.m.s.)’   Phase to ground   Ratio to the phase  Phase-to-
                                               kV (peak)4    to ground peak   phase   kV (peak)4
                                                             value as in   kV (peak)’
                                                             IEC 60071-1
                                               750           1.50
      275        300           380
                                               850           1.50         1275
                                              ________~                   1275  I
                                               850           1.50                    1050
      330        362          450
                                               950           1.50         1425       1175
                                               950           1.50         1425       1300
      400        420          520
                                                1050         1.50         1575       1425

                 550          620


                 800           830
                                                1425         1.70         2420    I   2100
      Notes  As in IEC 60071-1 and IEC 60694
      ‘IEC 60071-1 has specified only  V,,, values. Vr,,,s, is indicated based on the practices adopted by various countries.
      ’Lightning  stress between the phases is not more than the lightning stress between a phase and the ground. For more details refer to IEC:
      6007 1- 1.
      ’These  values are applicable for
        - Type tests - phase to ground
        - Routine tests - phase to ground and phase to phase.
      4More than one lightning impulse insulation level is indicative of the extent of exposure of an equipment to lightning surges.
      ’These  values aremeancfor type tests only.

      4 Rated continuous current ratings and         more than its actual maximum demand at any time. The
      permissible temperature rise                   reason is the liberal provisions made for loads that are to
                                                     be used occasionally - spare feeders, maintenance power
      The current ratings  should generally  be  selected  from   sockets and some reserve capacity available with most
      series R-10 of IEC 60059 which comprises the following   of the outgoing feeders. Moreover, some of  the feeders
      numbers;                                       may be operating underloaded.  To design a switchgear
                                                     assembly, particularly  for its  incoming  feeder and the
      1, 1.25, 1.6, 2, 2.5, 3.15, 4, 5, 6.3 and 8 etc. and their   busbar  ratings, based  on the connected  load  would  be
      multiples in  10                               neither economical nor prudent, and the protective scheme
                                                     too would under-protect  such a system.
      e.g.  for the  number  1.25 the  standard ratings  may  be;   Based  on  experience,  IEC  60439-1 has  suggested  a
      1.25,12.5, 125, 1250 or 12500A etc. IS 8084 has suggested   multiplying  factor,  known  as  the  ‘diversity  factor’ as
      the  following  ratings  in  amperes  based  on  the  above   noted in Table 13.4. This factor depends upon the number
      series:                                        of  outgoing  circuits and  is defined by  the ratio  of  the
                                                     maximum  loading  on  a  particular  bus  section,  at  any
      100,250,400,630, 800, 1250, 1600, 2000, 3150,   time, to the arithmetic sum of the rated currents of all the
      4000, 5000,6300, 8000, 10000, 12500 and  15000 etc.
                                                     outgoing  feeders  on  that  section  (Figure  13.14). This
                                                     factor also helps  to determine the most appropriate and
      The  temperature  rise  limits  of  the  various  parts  of  a   economical ratings of the main equipment, such as the
      switchgear assembly during continuous operation at the   transformer,  cables  or  the  bus  system,  associated
      rated current must conform to the values in Tables 14.5   switchgear and the protective devices (Example  13.1).
      and  14.6.                                     The  values  of  Table  13.4  are  based  on  a  general
                                                     assumption, and may vary from one installation to another
      Diversity factor                               depending upon the system design, the derating factors
      The connected load of an electrical installation is generally   considered and any other provisions made while choosing
   365   366   367   368   369   370   371   372   373   374   375