Page 533 - Industrial Power Engineering and Applications Handbook
P. 533

Captive (emergency) power generation 161507
        engine  fails  to  start  at  three  consecutive  attempts, the   (e)  Low lube (lubricating) oil pressure
        starting relay (SR) automatically locks out and emits no
        further ignition impulse. This feature is essential to protect   Electrical faults
        the engine against a possible hunting and a drain of the   (a)  Overcurrent alarm
        battery.                                       (b) Battery charger problems
                                                       (c)  Overcurrent and ground fault
        Switching off                                  (d) Reverse power supply
                                                       (e)  A fault condition in the differential scheme
        Bus voltage relay (Relay code 27) provides an impulse   (f) Breaker trip
        to the generator trip circuit as soon as normal  supply is
        restored. The generator falls out of the circuit automatically
        after a pause of  2-  10-30  seconds, and the engine stops.   Figure 16.11 illustrates a general arrangement of such an
        The relay now also has a delayed feature as it had during   AMF  panel  and  the  above  alarm  and  annunciation
        the start, to allow a pause to the main supply in case the   provisions.
        main  supply fails quickly again.
                                                       16.8.2 Electrical protection and metering
        Lubricating oil
                                                       The following protections and metering are considered
        An  interlock  is  provided  through  a  centrifugal type of   necessary for a DG  set:
        pressure switch (PS) to trip the engine in the case of low
        lube (lubricating) oil pressure during a run. Since during
        a start oil pressure has not built up, a timer, T, is introduced   For small ratings (say, up to 150 kVA)
        to bypass the trip interlock and avoid a false trip. A relay
        (contactor), d,, is  used  to  provide  lube  oil  pressure   Short-circuit protection  ~  through HRC fuses
        interlock.                                        Overcurrent-cum-short-circuit  protection,  through
                                                          thermal overcurrent and built-in short-circuit releases.
                                                          Figure  16.12 illustrates  a  general  protection  and
        Fuel oil solenoid valve (SV)                      metering scheme.
        This is to cut off the fuel supply to the engine on a trip   A kVAr meter to indicate the reactive power  of  the
        or a normal stop of the engine.                   circuit and to take corrective steps.  when necessary.

        Speed  and voltage control                     For medium ratings (say, up to 1000 kVA)
        Push button Nos 22 and 23 may be provided on the AMF   (a) Voltage-controlled overcurrent and ground fault
        panel and also on the remote panel to raise and lower the   protection (relay Code 51N/64)  By  a  three-pole
        speed and voltage,  when  required  to control the speed   voltage controlled  definite time delay relay  with  a
        cf;) and voltage (E,) of the generator in order for it to be   current setting of  50-200%  and a time delay range
        synchronized with another generator or an infinite bus.   of  0.1-1  second.  The  relay  is  typical  with  a
          Figure 16.10 illustrates a typical scheme incorporating   combination  of  an  overcurrent-time  relay  and  an
        all these features and interlocks.                undervoltage (u.v.) supervision unit. The purpose vf
                                                          the U.V. unit is to detect an U.V. due to a ground fault
        Notr                                              in  the  machine.  During  a  fault  the  relay  switches
        The above controls can also be achieved more precisely and almost   over instantaneously to a lower response current value
        instantly  by  applying  the  same  logic  with  the  use  of  PLCs,  as   and effects faster tripping. Typical characteristics can
        discussed  in  Section  16.13.                    be
                                                          - An overload characteristic say, 50-200%,  matching
         16.8  Protection of a DG set                       the  thermal  withstand  characteristic  of  the
                                                            generator.  This  operates  during  an  overlvad
                                                            condition when the generator voltage is normal.
         16.8.1  Alarm and annunciation (Figure 16.10)     - A ground fault characteristic determined by  the
                                                             U.V. unit monitoring the generator voltage. During
        Some or all  of  the following alarms and annunciations   a  ground  fault,  causing  an  u.v., the  same
        may be provided on the AMF panel, depending upon the   overcurrent  characteristic  is  reduced  to  another
        size of the DC set and the type of load it has to feed to   set value, resulting in a faster tripping, as desired.
        forewarn the operator. and prevent  a trip:

        Mechanical faults                              Note
                                                       The relay  can also be selected for a phase fault.
        (a)  Engine fails to start
        (b) Engine overspeeds
        (c) Engine  high  water  temperature  and  high  lube  oil   (b)  Reverse power supply protection (Relay Code 32)
           temperature                                    To detect a motoring action by a single-pole reverse
         (d) Low level of fuel                            power relay with a time setting of 2-10  seconds for
   528   529   530   531   532   533   534   535   536   537   538