Page 531 - Industrial Power Engineering and Applications Handbook
P. 531

Captive (emergency) power generation  16/505
        the output voltage. as it will adjust only its operating p.f.   a surge suppression device in  the rectifier assembly to
        (Section  16.9.1 B-2 and D-2). A difference in excitation   protect against such voltage surges.
        between  the  two  machines  when  operating in  parallel
        will cause a circulating current I, (Figure 16.15). It will   16.6.2 Non-linear loads
        add to one machine and subtract from the other, depending
        upon which machine is relatively overexcited, compared   Loads of rectifier, thyristor, UPS (uninterrupted power
        to the other.  The QDC, as discussed in  Section  16.3.4,   supply) and battery  chargers etc.
        will play the required role to limit the reactive loading of   Fluorescent tube lights.
        the two machines within permissible levels, when such a   All  such loads that have  non-sinusoidal  waveforms.
        situation arises.                                All  these  loads cause a  distortion  in  their  pure  sine
                                                         wave current waveforms. These distortions are termed
                                                         ‘harmonics’ and such loads ‘non-linear loads’. Thyristor
         16.6 Types of  loads                            and rectifier loads fall into this category and affect the
                                                         sinusoidal waveform of the generator voltage and distort
        The p.f. varies with the type of load. Here we discuss the   it. Typical voltage distortions in the output supply of
         likely  loads, their behaviour  and precautions that must   a  machine  as  a  consequence of  current  distortions,
        be taken  when  selecting a DG set for various types of   caused by  such non-linear loads are shown in Figure
        loads.                                           16.9 for a particular type of generator whose windings
                                                         have  a  pitch  factor  of  2/3  (which  suppresses third
        16.6.1  Linear loads                             harmonic quantities). The magnitude of distortions may
                                                         vary  with  other  machines  having  different  winding
        Such  as  motors  (not  really  but  can  be  considered  so   parameters. The distortion causes:
        being  balanced  loads)  heating  loads,  capacitor  and
        incandescent lighting loads etc. Of the linear loads, the
        following will  require special consideration.

        Motor loads
        These are highly inductive and cause heavy inrush currents
        during a switching operation, depending upon the type
        of starting being  adopted. The generator being  a high-
        impedance  machine,  application  of  such  high  current
        loads will cause a heavy voltage dip, which can be up to
         1 O-lS%  of the rated voltage, until the AVR acts to restore
        the  pre-set  value  of  the  terminal  voltage.  Although
        restoration  of  the  rated  voltage  is  rapid  due to  a  low
        response time of the AVR (of the order of 0.5-1  second)
        the generator is required to supply a much higher current,
        at  least for this duration. Consideration  must be given
        for all such loads on the system and their switching currents
        at the time of selecting the generator rating. A generator
        is generally suitable to carry a momentary but infrequent
        current inrush up to 2 to 2.5 times its rated current for
        hardly  10 seconds.

        Resistive  loads
        When  the  p.f. of  the  load  is  more  than  0.8, select  an
        enginc of  a higher rating, as noted earlier.
        Capacitive loads
        These  are  used  for  improving the  p.f.  of  the  system.
        When  they  are  installed  in  the  circuit,  they  must  be
                                                                    % Non linear load -
        switched OFF with the loads, to avoid a leading p.f. But   U’
        it must be ensured that the p.f. of the system does not fall   25   50       75      100
        below 0.8, otherwise it would overload the generator as          Courtesy: Crornpton Greaves
        well  as its field system.                          Winding parameters;
          During a switching operation, the capacitive reactance   Pitch factor - 2/3
        of  capacitors  and inductive  reactance  of the  generator   Sub-transient reactance, x:  - 12%
        may  resonate  and  cause  a  voltage  surge  in  the  field
        winding, as a result of transformer coupling between the   Figure 16.9  Voltage  distortion caused by different types
        armature and the field. This may damage the bridge diodes.   of thyristor drives  (with the use of  IGBTs, however, the
        The practice of  the leading manufacturers is to provide   distortion would be greatly reduced)
   526   527   528   529   530   531   532   533   534   535   536