Page 530 - Industrial Power Engineering and Applications Handbook
P. 530

16/504  Industrial Power Engineering and Applications  Handbook
                                                       which is normally selected for only 0.8 x kVA (kW = p.f.
                  'Yb
                                                       x kVA). At higher p.f.s, while the active component OA
                                                       of  the revised current OA"  remains the same as at 0.8
                                                       p.f., the generator will draw a lower current at  I& and
                                                       operate underloaded, while the engine will be fully loaded
                                                       and the DG set will deliver its optimum rated output. For
                                                       a  resistive  load  of  100 kW,  for  instance, operating  at
                                                       unity p.f.,  a generator rated for 100 kVA is not suitable
                                                       because the kW rating of the engine for a  100 kVA set
                                                 @= 0.8   will be only 0.8 x 100 i.e. 80 kW.
                                                        :.  The DG set (at least the engine) for such a load must
              Y                                        be selected for 100 x  1, i.e.  100 kW or 125 kVA.
           (i)  p.f. - unity     (ii) p.f. - 0.8 lagging
             VAvR - Marginally more   VAvR - Slightly more
                                                        16.5.3  PF leading
                                                       A generator is normally designed for a lagging p.f., and
                i"7                                    the armature reaction becomes magnetizing, and the field
                                                        is not suitable to operate at leading p.f.s. At leading pfs,

                                                        a leading p.f., therefore, the terminal voltage rises rapidly,
                          I                             system loses its control over the terminal voltage. During
                         VAVR                           as the  field  system  becomes  redundant,  rendering  the
                          I
               / d-                                     machine unstable. The field current reduces as the leading
                                                        p.f  reduces. When the leading p.f.  reduces further, say
                                                        from OC to OC' (Figure 16.8), the field current (excitation)
                 jcos@=o
                                  I/                    reaches almost zero, a condition known as self-excitation.
                                                        This is the critical point of  the AVR when  it  will  lose
                                   Y                    almost all its control. Any further reduction in thc p.f.
           (iii)  p.f. - Zero    (iv)  p.f. - Leading   will  cause  overexcitation,  causing  the  voltage  to  rise
               VAvR - Maximum        VAvR - Diminishes   steadily  without  any  control.  Leading  p.f.s  thus  cause
                                                        instability and rapid voltage rises.
         Figure 16.7  Phasor diagrams  for QDC, referred to the   The  above  situation  is,  however,  found  when  the
         secondary  side of the control transformer     machine  is  run  singly.  When  it is  operated in  parallel
                                                        with another source, the field excitation will not influence
         16.5  Guidelines on the selection of
               a DG set

         Several factors  are  important in the  performance of  a           Trajectory for maximum
         generator,  and  not  the  service  conditions  alone,  as           generator current, OA'
         discussed for motors, in Section 1.6. In addition to service
         conditions, the operating power factor plays a significant
         role  in  the  selection of a  DG set, as noted above. The
         following p.f. conditions may occur in practice, depending
         upon the type of loads connected on the system. Refer to
         Figure  16.8.

         16.5.1 PF lagging and less than 0.8
         The  active  component  of  current  OB  reduces  and  so
         does the kW rating of the generator. When the generator
         operates fully loaded, the engine operates underloaded
         but the reactive component BB' rises, requiring a higher
         level  of  excitation  (a higher field current),  which  may
         cause damage to the field system, which is designed for
         0.8 p.f.  lagging. It would thus require a derating of the
         complete machine indirectly. Generally, the derating may
         be of the order of 15% for a p.f. of 0.6 and 8% for a p.f.
         of 0.7. For exact deratings consult the manufacturer.
         16.5.2  PF between 0.8 and unity                  OA  - Maximum active component of generator = O.S/,
                                                           AA - Maximum reactive component of generator = 0.6/,
         The maximum kW rating of the DG set remains at 0.8 x   (if OA = /,)
         kVA, even when the p.f. of the system it is feeding rises
         to unity. This is due to a limitation in the engine capacity,   Figure 16.8  Effect of  PF on the output of a DG set
   525   526   527   528   529   530   531   532   533   534   535