Page 532 - Industrial Power Engineering and Applications Handbook
P. 532

16/506  Industrial Power Engineering and Applications Handbook
           1  Excessive heating of magnetic cores, as a result of   16.7  Starting of a DG set
             harmonic  frequencies due to  hysteresis  and eddy
             current losses (equations (1.12) and (1.1 3)).   16.7.1 Through an auto-mains failure (AMF)
           2  Overloading  of  neutral  conductors  due to  third
             harmonic currents flowing through the neutral. The   scheme
             size of the neutral must be increased by 150-200%   This is a common scheme to bring a standby DG set on
             of the normal  size in such cases, depending upon   line automatically on the failure of  the main  source of
             the severity of the harmonics.             supply  with  the  help  of  a  battery  backed-up  ignition
           3  Higher voltage stresses,  V, (equation (23.1))  may   scheme. On the failure of the main supply, generally three
             lead to dielectric breakdown.              ignition pulses are given to the engine to auto-start the
           4  Ageing  of  insulation  of  the  generator  and  other   machine. If the engine fails to start at three attempts, a
             equipment connected to such a system.      further pulse  is blocked.  To  start,  the  engine is  made
           5.  Noise and resonance problems (Section 23.5.2(C))   automatic. The generator excitation or the field current
             in  the  electrical  distribution  and  communication   is also pre-set, which adjusts the generator voltage to the
             networks.                                  required level automatically through the AVR. Provision
           6  Problems during a parallel operation due to distorted   is also made to start it manually in case the AMF scheme
             quantities  of  currents  and  frequencies.  Non-   fails and to also facilitate routine testing and give it more
             sinusoidal current will cause a non-linear impedance   flexibility. The scheme may be briefly described as follows
             (mostly  reactive)  voltage  drop  on  load  in  the   (see the control and scheme drawing in (Figure  16.10).
             generator windings. The terminal voltage will also
             contain harmonic quantities. It is possible that even   Control supply
             a fast-responding AVR may not be able to maintain
             the  required  sinusoidal  voltage  waveform  in  the   A  battery  backed-up  d.c.  source  of  control  supply  is
             whole cycle and cause circulating currents. Generator   provided  for the AMF panel  and engine  ignition. The
             manufacturers recommend that not more than 40%   control  scheme,  as  illustrated,  generally  consists  of  a
             of such loads be connected on the system at a time,   220 or 240 V a.c.  source of  supply,  with a transformer
             when the remaining  loads are linear.  To  suppress   rectifier unit, to provide a 24 or 48 V d.c. control voltage,
             the third harmonics, use of YlA or A/Y transformers   to charge the battery as required and a battery back-up of
             is  common  to  feed  such  loads  and  filter  out the   suitable capacity.
             third  harmonics.  For  more  information  refer  to
             Section 23.6.1.                            Selection scheme

         For all such loads, the machines will require a derating.   Auto or manual selection (switch SW2)
         For appropriate selection it is therefore essential first to   A switch SW2 is provided for the selection of the engine
         determine the content and magnitude of harmonics and   to be started in auto or manual modes:
         then to consult the manufacturer for the selection of the
         machine.  To  determine  the  magnitude  of  harmonic   Auto  mode   In  auto  mode  the  engine  starts
         contents. refer to Section 23.7.                 automatically  on failure of  the  a.c.  bus  voltage,  V,,
                                                          through an undervoltage  or bus voltage relay (Relay
                                                          code 27) (Figure 16.10). The relay is provided on the
         16.6.3 Special loads                             generator control panel with time delay contacts. Time
                                                          delay is provided to allow a pause to the generator if
         Loads of welding sets, which have intermittent duty cycles,   the normal supply is quickly restored.
         are  mostly  single phasc,  cause  low p.f.  and  stress the
         generator windings intermittently. Unbalanced loads, such   Manualmode
         as single phase loads, distributed unevenly cause current
         unbalance and low p.f.                         Local control
           All loads that may overstress the gcnerator windings   In manual mode, the engine can be started and stopped
         fall in this category  and call for special consideration.   locally,  through  a  pair  of  start  and  stop  push  buttons
         The manufacturer must be consulted for the right choice   Nos  17  and  18, provided  on  the  AMF  panel  (Figure
         of machine.                                    16.1 1).
           There are no ready-made formulae to deal with such a
         situation, except experience. It will largely depend upon   Local remote control (switch SW3)
         the  skill  of  the  engineer  to  make  the  right  choice  of   This is provided to facilitate the manual start and stop of
         machine to meet the requirements  in consultation  with   the engine from a remote point such as through a remote
         the manufacturer and also observing certain disciplines   station.
         as noted above, such as maintaining the p.f. between 0.8
         lagging  and unity,  suppressing  harmonics  as far  as  is   Three-attempts start
         practical, and maintaining a balance of loads. It is also
         desirable that neutrals are not interconnected when more   A  three-attempts  start  facility  is  provided  through  a
         than one machines is operating in parallel to eliminate   sequential  timer  (ST)  in  auto  mode.  A  starting  relay
         circulation of third harmonic currents.        (SR) gives three ignition impulses to the engine. If the
   527   528   529   530   531   532   533   534   535   536   537