Page 546 - Industrial Power Engineering and Applications Handbook
        P. 546
     16/520  Industrial Power Engineering and Applications Handbook
          the bus or vice versa. The machine will only float on                           \
          the  bus  and  the  PM,  will  be  supplying  only  the
          mechanical losses, (Figure  16.24(c)).
        D performance on-load
        (Considering GI as the incoming machine and referring
        to Figure  16.15)
        1  By changing the driving torque or power input
          Fixed parameters   vb, fb,  Z,  = 0, and Z1
           Variable parameters  Zl and cos &, while El will have
                           a fixed magnitude but variable
                           phasor disposition.
           When the power input to PMI is increased, the output
           of  GI increases.  Since El is constant  at a particular
           excitation, it  changes its phasor  location  only  with
           respect to V,.  With a change in power input, therefore.
           El traverses  through  a fixed trajectory  as shown in
           Figures  16.25 a and b,  and with it changes its load
           angle, el, load current,  ZI and p.f.  cos 4,. We  have
           considered  four  possible  conditions,  to  define  the
           performance of the machine, under different levels of
           power input:
            When El is ahead of  V, At  a load angle 8, the
            load current, 11, will lag vb by an angle 41 (refer to
            Figure 16.25(a)). II is still considered to be lagging
             Ef  by  almost 90", although  it  may  be  better  on
             load.
            With the increase in the power input, E, will advance
             further  and improve its p.f. At  one stage, the p.f.
             will become unity and beyond this it will start leading
             (Figure  16.25 (b)). Incidentally, the maximum p.f.
             is achieved when the load angle el becomes 90",
             which is also the limiting  stage, beyond which it
             would  become  an  unstable  region,  as the  exciter
             would cease to exercise any control over the voltage.
             At this point, refer to parameters  E[, EA, I:,  @{ and
             e;  as 90".
              Any condition beyond unity p.f., i.e. GI > 0, would
             mean ZI leading  and can  compensate the reactive
             power of the system and improve its p.f. The machine
             is now called a synchronous condenser (capacitor),
             which  besides  supplying  power  to  the  main  bus,
             will  also  improve  the  system  p.f. The  above,
             however, is only a theoretical analysis. A generator
             designed for 0.8 p.f. lagging is not suitable to operate
             at  a leading  p.f.,  as the  excitation  system  would   11"
             cease to exercise any control over the voltage. The             (b)
             voltage rises rapidly beyond unity p.f. as a result of
             positive armature reaction (Section  16.4). When a   Figure  16.25  Performance of  generator GI by varying its
             generator is required to operate at leading p.f.s, its   driving torque on load
             field system must be designed for leading p.f.s.
             When, however, the power input to PMI is reduced,   the bus and the PM, supplies primarily only its no-
             GI will  gradually  offload.  Consider  the  situation   load losses.
             when El, falls in phase with vb. (Refer to parameters   For  the  sake  of  argument,  if  the  power  input  is
             E:, E,", 0:  = 0 and  I:  at 4'  in Figure  16.25(b).)   reduced further, say by removing PMl totally from
             GI will now feed no power to the bus, nor receive   the generator,  E;'  will fall behind  vb and  I;  will
             any power from it. GI is now termed as floating on   lead  vb.  (Refer  to  parameters  E:,  ET, e;  and
     	
