Page 547 - Industrial Power Engineering and Applications Handbook
P. 547

Captive (emergency) power generation  161521
              /,"at  @:   in Figure l6.25(a).) The machine will now
             operate  as  a  synchronous motor  rather  than  as  a
             generator and will absorb reactive power from the
             bus.  Since  the  generator  operates  once  again  at
             leading p.f.s, the same condition will apply as noted
             above.
         2  By changing the excitation (field current)
           Fixed parameters   V,, jj,, Z, = 0 and Z,
           Variable  parameters  E,, I, and cos 4,
             The  same theory would apply as discussed ahove
           in the case of two generators. Since there is no variation
           in the power input to PM,, the output of generator G1
           will remain the same, except for the marginal variation
           in the copper losses as noted  earlier:
                                                                                     I
            :.   I, cos 4,  = I; cos @;  = I('cos  @('= constant          p f  leading region 1  p f  lagging region
           In other words, for the same bus voltage, V,, the active
           component of  the  current for GI would  remain  the   Figure 16.26(a)  Phasor diagram
           same while  the  reactive component  I, sin 4, I,'  sin
            4' or /('sin  4"  and therefore the reactive power (kVAr)
           would continue to vary. A change in excitation will
           change E, and its load angle   (Figure  16.26(a)) and
           consequently  will change I, and its p.f., cos @,. The
           following Dossibihties  mav arise:
             When-dl  operates at  uhty p.f.  is the  most  ideal
             condition. The  generator  will  now  deliver  its
             maximum  power  at  the  least  current  value.  The
             machine is least  stressed for its best  performance.
             GI is ahead of the bus and is only sufficiently excited
             such that cos @I  = 1  and
             E, = v,  + 7, gd, or E, cos 8, = V,
             When  GI is  overexcited,  E, rises  to  E;  and the
             machine  starts to operate at lagging p.f.s,  so that
             E,'  cos 8; > V,,  and  cos 8,'  > cos 8,.
             When  GI is  underexcited,  El will  reduce  to  E('               -
                                                                      - I
             and  the  machine  will  start  to  operate  at  leading   p.f leading region  I  p.f lagging region
             p.f.s, so that  E('cos  e('<  V, and cos  8:  < cos 81.   (under excitation)   (over excitation)
             All these conditions are illustrated in Figure 16.26(a).
             In all three cases, the active component of current,   Field current vs armature current
             OA, remains the  same. A  higher  current than  the
             active component, either lagging  or leading,  is  a   Figure 16.26(b)  Variation in the load current of  G, with the
                                                       change in the excitation on load
             loss  component.  It  is  desirable  to  operate  GI as
             close to unity p.f. as possible to keep this component
             at its lowest. The variation in the generator current,   source, which  can  be  another  generator or  an  infinite
             I, versus field current, is shown in Figure 16.26(b).   bus,  it  is  essential  to  first  fulfil  the  following  basic
             When the current II is leading, the machine absorbs   conditions, to avoid a possible voltage or current transient
             reactive  power  and  operates  as  a  synchronous   condition  which  may  occur  and cause  electrodynamic
             condenser and  in  addition  to  supplying  its  active   forces in the generator and damage its armature or affect
             power to the system also improves the system p.f.   adversely  other machines,  connected on the system or
             But, as noted above, for operating a generator as a   the bus system itself.
             synchronous condenser, its field system has to be
             designed accordingly.                      1  The phase  sequence of  the incoming machine  must
                                                          be  the  same as  that of  the existing  source (Figures
                                                          16.27(a) and (b)).
         16.1 0  Procedure of parallel operation       2  The terminal  voltage, E,, of  the  incoming  machine
                                                          must he almost the same as that of the other machine,
         16.10.1  Synchronization                         E2 or the bus,  V, (Figure  16.27(c)), i.e.
         Before switching an incoming generator on an existing   E, = E2 or  V,
   542   543   544   545   546   547   548   549   550   551   552