Page 554 - Industrial Power Engineering and Applications Handbook
P. 554

16/528 Industrial Power Engineering and Applications Handbook
           We will notice during our subsequent discussions that   - Alarm
           E  and  I  cos  @  are  complementary.  Although  I  and   - Annunciation etc.
           cos @cannot be altered directly, they are both functions   Even the grounding of the generators can be monitored
           of  excitation  voltage E.  A  variation  in  E  will  vary   through  this  scheme,  so  that  only  one  machine  is
           both I  and cos@. The reactive or kVAr loading is thus   grounded at a time, to avoid circulation of fault currents
           dependent  upon  the  voltage  versus  reactive  load-   (Section 20.10.1).
           current characteristics  of  the generators  and can be
           varied through the QDC. Thus the power generated   Example 16.2
           or the load sharing by  a generator can be altered in   Consider two DG sets operating in parallel and having the
           the following ways;                         following parameters:
           Active  power  (kW)  sharing   By  changing  the
           mechanical torque  of  the prime mover by  changing        G1             G2
           its driving force (fuel supply).
           Reactive  power  (kVAr) sharing  By  changing  its   Rating   750 kVA     750 kVA
                                                       p.f.
                                                                     0.8 lagging
                                                                                     0.8 lagging
           excitation (field current) that will alter the generated   Speed at full load  1500 r.p.m. (50 Hz)  1500 r.p.m. (50 Hz)
           e.m.f., E, in both magnitude and phase displacement,   Droop   3  Yo      4 %
           fremaining  the same. A mismatch in excitation will
           result  in  reactive  unbalancing,  causing  a  reactive   To  determine the  load sharing  between the  two, draw the
           circulating  current,  which  is  not  desirable.  It  is   drooping curves as shown in Figure 16.37.
           controlled through QDC by adjusting the droop even
           for identical machines.                     For    G1: FF, = no-load speed = 1.03 x  1500
                                                                    = 1545 r.p.m.
         16.13 Total automation through PLCs           and   frequency = 1.03 x 50
                                                                  or 51.5  Hz.
         With  the  availability  of  PLCs  (Programmable  Logic   FF, = full-load speed
         Controllers,  Section  13.2.3) it has become  possible  to   = 1500 r.p.m.  at a frequency of  50 Hz.
         perform  all  the  above  controls  and  protections
         automatically. The generating station  can  even  be  left   FDA, = full active load
         unmanned. Such schemes can be adopted for large captive    = 750 x 0.8
         generating stations or where a quicker and more accurate   = 600 kW
         power supply is desirable,  such as large process plants
         (cement, paper, chemicals and refineries) which may have   Similarly for  G2:
         large captive generating units (two and more).          FF, = no-load speed = 1.04 x  1500
          When there are two or more machines it is also possible
         to program the PLCs to select the machine to perform in    = 1560 r.p.m.
         a particular  sequence so that each machine has almost   and   frequency = 1.04 x 50
         the  same number of  hours of  operation. This makes it    = 52 HZ
         easy to identify the next machine for routine maintenance
         shutdown. A  PLC  is  fully  capable  of  performing  the
         following;
           To  auto-start  the  machine  in  the  same sequence  as           e
           discussed in Section 16.7.
           To initiate operation of the next due machine when the
           power demand on the existing machine or bus exceeds                 52 Hz
           its rating.
           To  perform  all  the  duties  of  an  auto-synchronizing
           relay and monitor and correct AV, Afand  A@.
           To run the incoming machine a little in advance, while
           switching it on the bus, to enable it share a part of the
           load  immediately  from the  existing  machine  or  the
           bus.
           The duty of load sharing between two or more machines
           is performed similarly.
                                                                                    -
           When  the  load  demand  falls, the  machine  that  has
           operated for more hours is stopped first.     600   400    200     ,    200   400    600
           Any required sequence or programming is possible.        kW               kW
           The scheme can also be provided with the required      u                  Gi
                                                                     G2
           - Metering
           - Protection                                 Figure 16.37  Determining the load sharing between G1 and
           - Indication                                 G2 with the help of  prime-movers drooping characteristics
   549   550   551   552   553   554   555   556   557   558   559