Page 655 - Industrial Power Engineering and Applications Handbook
P. 655

18/620 Industrial Power Engineering and Applications Handbook
        Example 18.5                                  (A) Checking for the protective level
        Step-by-step selection of  a surge arrester for the protection
        of equipment  mounted on a 400 kV transmission  line.   For this rating, the arrester protection levels are:
        Considering conditions (i) and (ii) occurring at the same instant,
        :.  total TOV = 1.4 x  1.1 = 1.54 for 3 seconds   Vres(max) for a switching impulse wave of  1 kA
                                                          for the purpose of energy capability = 654 kV.
        TOV factor as in Figure 18.16(b), K= 1.13
                                                          For switching impulse protective margin at 2 kA
                                                          = 676 kV.
                                                          Vres(max) for a 20 kA lightning impulse (8/20 ps)
        For this voltage, we have selected a Class 4 arrester, which   = 844 kV.
        has the nearest next higher rating as in Table  18.11 as   Vre,(max)  for a 0.6 ps FOW from Figure 18.20
        V,  = 336 kV                                      = 1.12 x 844 = 945 kV.
                                                          BIL of  the equipment to be protected, from Table  13.3
        As regards the primary selection of the arrester, it is complete   list I  (considering the lower side to save on the cost of
        at this stage. But this selection must be checked for its adequate   equipment)
        protective level and the energy absorption  capability
                                                          For switching surges  = 950 kV
                                                          For lightning surges  = 1175 kV
        Considerations               Data
                                                          For very fast-rising surges (FOWs)  = 1175 kV (assumed).
        Nominal system voltage (4)   400 kV(r.m.s.)       This value must be obtained from the manufacturer of
        Maximum system voltage  (V,)   420 kV(r.m.s.)     the equipment to be protected.
                                                &
        In per unit (P.u.)           1 p.U. =  420 x  -   To  check the protective margins:
                                                6
                                     = 343 kV
        Maximum continuous operating
        voltage (MCOV),  7 vrn  = vc   420
                                     6
                                     ~   = 243 kV
                                           (max.)
                                                          Type of    Margins    1  Margin   Suitability
                                                          surge      recommended  available   of  the
        Temporary overvoltages (TOVs)   OV   tripping                as in Table          arrester
        as in Table 18.5             factor   time                   18.2
         (i)  Due to a ground fault for a
           solidly grounded system with
           a GFF of  1.4    TOVl     1.4   3 sec        (i)  For switching  1.15   950 = 1.40  OK
                                                                                 676
         (ii)  TOV due to load rejection                  surges
                            TOV2     1.1   1 sec       (ii)  For lightning   1.05   -- 1175 - 1.39  OK
                                                                                 844
        (iii)  TOV due to a short-circuit                 surges                 -- 1175 - 1.24 OK
           fault            TOV3     1.1   3 sec       (iii)  ForFOWs   1.15     945
        Table 18.11  Protective characteristics of  a gapless station class surge arrester for,  (1) Line discharge class 4, and (2) Single
        impulse energy capability = 7 k.J/k.V,

        System  Rated   Max.   MCOV   TOV capability   Maximum residual voltage with current wave
        voltage  voltap  cont.   as in   for
                       operating ANSI
                       voltage  tests              Switching surgesa   Lightning surges 8/20 ps
                       (CO  V)
                                                   1 kA   2 kA   3 kA   5 kA   10 kA   20 kA  40 kA
                                                   kVpeak   kVpeak   kvpeak   kVDeak   kVDeak   kVDeak   kvpeak
        420    330    264     267    383    363    642    664    680   71 8    759    829   91 1
               336     267    272    390    370    654    676    693   73 1    773    844   928
               360     267    291    418    396    701    724    742   783     828    904   994
                                                                                     ~
               372    267     301    432    409    724    748     767   81  0   856   934   1027
               378    267     306    438    416    736    760     779   823    870    949   1044
               381    267     308    442    419    74 1   766     785   829    877    957   1052
                                                                                     ~
               390    267     315    452    429    759    784     804   849    897    979   1077
               396    267     318    459    436    771    796     816   862    911    994   1093
               420    267     336    487    462    817    845     866   914    966    1055   1160
        aAny impulse with a front time longer than 30 ps.
        Courtesy: ABB
   650   651   652   653   654   655   656   657   658   659   660