Page 455 - Instrumentation Reference Book 3E
P. 455

438  Electrical measurements

            Table 20.5  Electronic multimeter specification
            D. c.  voltmeter
            Voltage ranges: f 15 mV to f 1500 V full scale in  15, 50 sequence (1 1 ranges)
            Accuracy: f2% of full scale on any range
            Input resistance: 100 Mn ?C  1% on 500mV range and above, IOMR f 3% on 150mV range and below
            A. c.  voltnzeter
            Voltage ranges: 0.5V to 300V full scale in 0.5,  1.5, 5 sequence (7 ranges)
            Frequency range: 20 Hz to 700 MHz
            Accuracy: &3%  of full scale at 400 Hz for sinusoidal voltages from 0.5 V-300  V rms. The a.c. probe responds to the
            positive peak-above-average value of the applied  signal. The meter is calibrated in rms
            Frequency response: ?C2% from 100 Hz to 50 MHz (400 Hz ref.); 0 to -4%  from 50 MHz to 100 MHz; &lo% from
            20Hz to 100Hz and from 100MHz to 700MHz
            Input impedance; input capacitance 1.5 pF. input resistance > 10 MR at low frequencies. At high frequencies,
            impedance drops off due to dielectric loss
            Safety: the probe body is grounded to chassis at all times for safety. All a.c. measurements are referenced to chassis
            ground
            D. c.  ammeter
            Current ranges: 51.5 pA to Ik150mA full scale in 1.5, 5 sequence (1 1 ranges)
            Accuracy: &3%  of full scale on any range
            Input resistance: decreasing from 9 kR  on 1.5pA range to approximately 0.3 R  on the 150mA range
            Special current ranges: +1.5,f5 and *15pA  may be measured on the 15, 50, and  150mV ranges using the d.c
            voltmeter probe, with &5% accuracy and  lOMR input resistance
            Olimmeter
            Resistance range: resistance from 100 to  10Ma center scale (7 ranges)
            Accuracy: zero to midscale: Ik5%  of reading of &2Yo  of midscale, whichever is greater; Ik7% from midscale to scale
            value of 2; &8% from scale value of 2 to 3;  &9yo from scale value to 3 to 5; 510% from scale value of 5 to IO
            Maximum input: d.c.: IOOV on  15, 50 and  150mV ranges, 500V on 0.5 to 15V ranges,  1600V on higher ranges.
            As.: 100 times full scale or 450V p, whichever is less


                                                     construction  minimizes  the  magnetizing  current,
                                                     iron loss, and leakage flux, ensuring that the actual
                    Pointer
                                                     primary to secondary current ratio is close to the
                                 er                  inverse-turns ratio.
                                                       Figure 20.17(c) shows the effect of magnetizing
                                                     current and iron loss on the relative magnitudes
                                                     and  phases  of  the  primary  and  secondary  cur-
                                                     rents.
                                                       Two  errors  of  cts can  be  identified in  Figure
                                                     20.17(c). These are the current or ratio error and
                                                     the phase angle error or phase displacement. The
                                                     current or ratio error is defined as
                                                         Rated ratio (Zplls) - actual ratio (Zp/ls)
                                                                Actual ratio (Zplls)   x 100%
                                                     The phase-angle error or phase displacement is the
                                                     phase  angle between the primary  and secondary
                                                     current phasors drawn in such a way (as in Figure
                                                     20.1 7(c)) that for a perfect transformer there is zero
                                                     phase displacement. When the secondary current
                                                     leads the primary current the phase displacement is
                                                     positive.
                                                       These  errors  are  expressed  with  respect  to  a
                                                     particular  secondary  load  which  is  specified by
                                                     its burden  and power  factor. The burden  is the
                                                     VA rating of the instrument at full load current.
                              chamber                A  typical  burden  may  be  15 VA  with  a  power
                          (b)                        factor of 0.8 lagging. Figure 20.17(d) shows typ-
            Figure 20.15  Moving-iron instrument. (a) Attraction;   ical current  and phase  angle errors for a ct as a
            (b) repulsion (fromTagg1974).            function of secondary load current. BS 3938:1973
   450   451   452   453   454   455   456   457   458   459   460