Page 152 - Mathematical Models and Algorithms for Power System Optimization
P. 152

Load Optimization for Power Network 143

               (3) Line load output result: including name of bus at both ends, number of circuits, reactance
                    (per-unit value), safety current, carrying current, and load capacity; thus, the line of
                    HONGXING-1 to XIAOTANG-1 and NANHAI-1 to WUCUN-1 has reached 90% of its
                    upper limit, as shown in Table 5.20.



                  Table 5.20 List of lines whose carrying current is up to upper limit after LCO for a certain
                                                state of the real case
                                                      Reactance
                                                       (Per-Unit  Safe Current  Carrying  Load Rate
                           Bus             Circuit No.  Value)      (A)     Current (A)    (%)

                HONGXING-1    XIAOTANG-1                0.0211      575        517         90
                NANHAI-1       WUCUN-1                  0.0387      494        445         90



               (4) Transformer load output result: including name of bus at both ends, parallel No., reactance
                    (per-unitvalue),maintransformercapacity,andpowerandloadcapacity;thus,2#transformer
                    atZIDONGSubstation,1#and2#transformersatZHUYUANSubstation,and1#transformer
                    at HONGXING Substation have reached 90% of the upper limit, as shown in Table 5.21.



                   Table 5.21 List of transformers whose load is up to upper limit after LCO for a certain
                                                state of the real case
                                                                  Main
                                                     Reactance  Transformer
                                                     (per-unit   Capacity
                          Bus           Parallel No.  value)      (MVA)    Power (MW) Load rate (%)

                ZIDONG-2     ZIDONG-1       2         0.0727       180         162         90
                ZHUYUAN-2   ZHUYUAN-1       1         0.0583       240         216         90
                ZHUYUAN-2   ZHUYUAN-1       2         0.0583       240         216         90
                HONGXING-   HONGXING-       1         0.0947       150         135         90
                2                1
                HONGXING-   HONGXING-       2         0.0953       150         134         89
                2                1



               This chapter sets load weights as equal values in both the 5-bus test system and the real 74 bus
               system. However, in actual operation of an urban grid, the “weight” of some important users is
               indeed high, and even the load cannot be curtailed in any system state. In such a case, the weight
   147   148   149   150   151   152   153   154   155   156   157