Page 272 - Modern Control of DC-Based Power Systems
P. 272

Simulation                                                   233


              and settling time while the LQG-Centralized control exhibits the highest
              voltage drop. The LSF exhibits the slowest dynamics due to the chosen
              dynamics through pole placement and the nonlinearity compensation. All
              three decentralized virtual disturbance-based controls display a behavior
              comparable to that already observed in the cascaded system setup and
              show in all aspects better performance compared to the centralized LQG
              formulation. Characteristic values, like those calculated in the cascaded
              system, are presented here in Table 6.6. It should be clarified that due to
              the steady-state error the numerical values are calculated for the end value
              of voltage and current, taken at t 5 0.39 s.
                 To avoid the steady-state error after the load increase two options are
              possible. One could be to design a prefilter, which actually can only be
              designed for a specific load level and would mean that at other load levels
              an over- or undervoltage appears. The alternative is the implementation
              of a secondary control loop consisting of a PI controller with the feed-
              back of the bus voltage as mentioned in Subsection 6.2.1. The latter
              option was chosen.
                 It’s to be pointed that the introduction of a Droop PI outer control
              loop for steady-state error suppression will lead to a change in transient
              behavior as another control loop interaction is introduced. The corre-
              sponding results can be analyzed in Figs. 6.12 and 6.13 where the reader
              can observe that due to the additional PI-Loop the Centralized LQG
              improves in performance; this resides in the fact that the centralized for-
              mulation profits more from an adjusted voltage setpoint. For the other
              controllers the decrease in voltage drop corresponds directly with the
              reduction in steady-state error. The rise times for the decentralized virtual
              disturbance and Synergetic control are 0.0022 s, while for the Centralized
              LQG it is 0.0032 s, and for the LSF it corresponds to 0.0037 s.
                 After presenting the possibility of mitigating the steady-state error in
              the bus voltage, all further test cases are performed without the
              Droop PI as its inclusion would deviate the analysis from a pure stabiliz-
              ing action point-of-view towards a system level analysis, and in certain
              combinations retuning control coefficients would be necessary.
                 In an ISPS consisting of multiple LRCs also the case of a loss of avail-
              able generation capability needs to be considered. At the time instant
              t 5 0.3 s LRC 3 is disconnected and LRC 1,2 are accountable to supply the
              30.9 MW load. Thus, the load factor is 0.515 of the installed power
              before and 0.775 after the reduction of installed power. The results for
              the control strategies are shown in Figs. 6.14 and 6.15. Those results
   267   268   269   270   271   272   273   274   275   276   277