Page 270 - Modern Control of DC-Based Power Systems
P. 270

Simulation                                                   231


              Table 6.5 Shipboard Power System Parameters (Matlab)
                                            LRC 1,2,3 (Buck)         POL (Buck)

              P n (MW)                      20                       60
              V in (kV)                     8.91                     6
              V out (kV)                    6                        3
              f s (kHz)                     1                        1
              R f (mΩ)                      99.7                     33.2
              L f (mH)                      2.1                      1.1
              C f (μF)                      659.72                   2000
              C if (μF)                                              3608
              Base load (MW)                2.8
              Load increase (MW)                                     22.5






              features the control implementations of Chapter 1, Overview—Voltage
              Stabilization of Constant Power Loads (CPLs). The converter models are
              simulated using averaged converters models. The simulations were run
              with the system parameters stated in Table 6.5 which are based on [12].
              The test cases are reflecting large changes in the operating conditions; on
              one hand the sudden connection of large amount of load, and on the
              other hand the unexpected disconnection/failure of available generation
              capacity.
                 At this stage it should be clarified, that each control could exhibit
              varying performances in terms of overshoot, undershoot, settling time,
              rise time, and oscillations, depending on the selection of its control coeffi-
              cients. The scope of this overview is to highlight that decentralized con-
              trollers do not necessarily perform worse than centralized controllers and
              that under simplified conditions stabilization with good results can be
              achieved by decentralized control architectures, while the system under-
              goes large signal perturbations.
                 The three LRCs have a load sharing of 33%/33%/33% set via droop.
              For evaluating the achieved control performance with respect to guaran-
              teeing DC bus stability the load demand of the POL converter was
              increased in two steps. Starting from a base load of 2.8 MW per LRC,
              which is has be selected to guarantee CCM, the load demand is increased
              by a step of 22.5 MW at the time instant of t 5 0.1 s resulting in a load
              factor of 0.515.
                 The second increase in load demand occurs at t 5 0.25 s with same
              step size, this results in a load factor of 0.89 which is equal to a load
   265   266   267   268   269   270   271   272   273   274   275