Preparation and Use of Performance Standards  443





                   INSTALLATION:         PERFORMANCE STANDARD: EMERGENCY SHUTDOWN SYSTEM (cont.)
                   Component                   Test & Frequency           Assurance
                   Inter-ESD System   A dedicated dual redundant data link connects the ESD systems on the   Verified through inspection
                   Communication Checking  nearby installations [if any] to carry intertrip signals identified on the   and testing.
                                   cause and effect charts.            ReferenceESD
                                                                       Maintenance Routines.
                   Computers I/O devices  Regular shutdown path checking from the system inputs to the system   System is self-checking in
                                   outputs is automatically carried out by the system at a frequency   accordance with Functional
                                   sufficient to ensure system faults are detected, alarmed, and executive   Design Specification for
                                   actions taken to achieve the availability/ reliability requirements of the   Emergency Shutdown
                                   ESD system.                         System
                                                                       Regular function testing of
                                                                       ESD System
                   Computer control  Each system is subdivided into a solid-state logic system for Category 1   Instrument Based
                                   signals and a programmable system for Category 2 signals.  Protective Systems
                                                                       IEC 61511:2016
                   Survivability                Requirement               Assurance
                   ESD Level 0     Emergency systems and essential services with Ex d protected built in   Functional Design
                                   power supplies would be left operational, including:   Specification  for
                                     emergency lights                  Emergency Shutdown
                                     navigational aids                 System
                                     PA/GA systems
                                   Additionally the diesel firewater pumps would remain operational until
                                   the diesel supply was exhausted.
                   Fire & Explosion  Risk Evaluation and Protection Philosophy Study -ESDVs and   Risk Evaluation and
                                   Blowdown valves rated to API specification.  Protection Philosophy,
                                                                       Design drawings and
                                                                       inspection.
                   UPS             Providing electrical power to computer systems  See UPS performance
                                                                       standard
                   Hydraulic Valves  Provide isolations
                   Pressure Relief System  Reduces pressure in the process equipment and reduces loss of inventory.  See pressure relief
                                                                       performance standard
                   Fire and gas detection  Initiates ESD shutdown      See F&G performance
                                                                       standard
                   Hazardous Area Certified   Ex rated equipment in place  See Hazardous Area
                   Equipment                                           Equipment performance
                                                                       standard
                   HVAC            Executive actions carried out by ESD on HVAC system  See HVAC performance
                                                                       standard
                      Environmental              Justification            Reference
                          ESD      Sectionalises the plant in the event of a hazardous situation occurring, in   Cause & Effect Matrix
                                   order to reduce the potential escape of environmentally hazardous
                                   inventory
                   Excluded components           Justification            Reference
                   Emergency Power  All systems are fail safe or UPS maintained  See UPS performance
                                                                       standard