442    CHAPTER 2  Preparation and Use of Performance Standards






                            INSTALLATION:      PERFORMANCE STANDARD: EMERGENCY SHUTDOWN SYSTEM (cont.)

                          Functions                       Element                Assurance
                            Reliability & availability                           Reference
                          The ESD system is a Category 1 safety system which provides protection of personnel and the installation, as  Installation Safety Case
                          defined in the maintenance management strategy. Test and maintenance procedures have been prioritised
                          accordingly to provide a high integrity ESD system and are contained within the maintenance management   SIL Assessment Report
                          system. The nominal ESD system availability is 99.997%.
                          Contracts with Health Care providers specify reliability targets which are continuously under review.
                              Component               Test & Frequency           Assurance
                          Shutdown Field Devices    2/n voting is fed into the ESD system for initiation. The ESD system does   Verified through inspection
                                          not rely upon cascade effects to produce shutdowns of related process   and testing.
                                          systems.                            Reference ESD
                                                                              Maintenance Routines
                          ESD             The ESD system is fail safe and line monitored. The ESD system is   Verified through inspection
                                          designed to fail to safety on fault detection in any single channel section of  and testing.
                                          a shutdown path.                    Reference ESD
                                                                              Maintenance Routines.
                                          Level 3 - six monthly; Other levels - yearly
                          Cabling and Power    A hardwired matrix displays the status of system inputs, outputs, override   Verified through inspection
                                          and reset status and the health of the system.   and testing.
                                                                              Reference ESD
                                          The system monitors the status of power supplies and shutdown paths and   Maintenance Routines
                                          alarms all faults. A single channel fault in any section of the system
                                          produces a fail-safe response.