Page 387 - Boiler_Operators_Handbook,_Second_Edition
P. 387

372                                                                               Boiler Operator’s Handbook


               will open to admit air if the beam is rotated clockwise  change of the signals where the output has to change
               or close off the air supply and stop while the beam  twice as much as the input. That’s the concept of propor-
               continues to rotate counterclockwise. Further counter-  tional control and in this case the controller has a gain
               clockwise rotation will open the bleed end of the valve  of two which means the output has to change twice as
               to dump air to atmosphere.                           much as the input. Now the controller will run the water
                    Let’s start with proportional control. That’s where  valve from closed to open with half the change in the
               the output of a controller is proportional to the differ-  output of the level transmitter, between 25% and 75% of
               ence between the process value and the setpoint. As-  the signal range.
               sume we’re using the level transmitter covered earlier to     We could increase the gain until there was very
               produce the process value so, in this case, our controller  little change in process value to produce a full stroke
               will be used for level control. We’ll also assume the level  of the water control valve so the water level would not
               control valve is reverse acting so an increase in control-  vary much. If we did that it wouldn’t work too well be-
               ler output will close the valve. When the water level in  cause any little ripple in the water level would produce
               our tank increases the control signal decreases. To make  a dramatic change in the valve position and we would
               the system work any increase in process value should  have a lot of valve wear. We would also have controller
               result in a increase in output to close the valve. Now  “noise” where the output is jumping around with little
               we can look at the ratio totalizer to see how to connect  relationship to the actual level in the tank.
               the process variable. The output bellows pushes up on     Conversely we could reduce the gain to something
               the right side of the beam so any increase in output will  less than one which would create another problem; the
               tend to rotate the beam around the pivot in a counter-  water valve would never close. It might work during
               clockwise direction. It’s a pressure balance system so the  normal plant operation but when the plant is shut down
               process variable has to create a tendency to rotate the  the controller output couldn’t increase enough to close
               beam in the opposite direction to balance the forces.  the valve. Too much gain produces a lot of noise and er-
                    If the beam tends to rotate clockwise more air is  ratic operation while too little gain can result in failure
               supplied to the output and output bellows to counter  to operate at the extremes of load.
               that rotation. If it tends to rotate counterclockwise the     One problem with this controller arrangement is
               vent valve opens to decrease the output. Connecting the  we have no way to adjust the setpoint. For all practical
               signal from the transmitter to the bottom bellows (A)  purposes the setpoint is the center of the transmitter’s
               does the job. Now a change in the level will produce a  position. In order to have an adjustable setpoint we use
               change in the output of the controller to open or close  the B bellows of the controller and supply it with a con-
               the control valve. As shown the controller acts pretty  trol signal that is adjustable. The setpoint signal in this
               much like a signal booster because it produces a change  case is produced by a simple air pressure regulator. By
               in output that precisely matches a change in input. As  connecting the regulator to the bellows opposite the one
               the level transmitter output changes from minimum  sensing the signal from the transmitter we have devel-
               to maximum the controller output produces the same  oped a setpoint controller.
               value because the bellows areas are identical. It works     Now the output of the controller is proportional to
               pretty much like our float controller, requiring the level  the difference, what we call the error, between the set-
               change over the full range of the float to position the  point and the transmitted level signal. Instead of acting
               control valve between open and closed.               only on the pressure from the float transmitter the action
                    The whole reason for using a control system is to  is dependent on the difference between the setpoint and
               improve on the operation we get with a float control  the process variable. The setpoint pressure acts on the
               valve so let’s see what we can do with it. We can reduce  diaphragm at B pushing down on the right end of the
               the change in level by moving the pivot on the controller  beam opposite the process variable signal coming in at
               closer to the output end. It works just like a teeter totter.  A. The force tending to rotate the beam is equal to the
               Let’s adjust the controller so the distance from the center  difference between the two pressures times the area of
               of the process input to the pivot is twice the distance  one diaphragm.
               from the output bellows to the pivot (two thirds of the     All modern controllers operate on the error, not
               beam length). Now, if the level varies to produce a 1 psi  the actual signal value. Now changes in output are
               change in the transmitter output the controller output  proportional to changes in the error, not changes in the
               has to change by 2 psi to maintain the force balance in  level. An important part of this to understand is you can
               the controller. There is a proportional difference in the  introduce an error by changing the setpoint. We’ll need
   382   383   384   385   386   387   388   389   390   391   392