Page 388 - Boiler_Operators_Handbook,_Second_Edition
P. 388

Controls                                                                                            373


               to set the gain to much more than two in this case or the
               output may not change enough to fully stroke the valve.
                    Creating a setpoint controller allows us to use
               something  more than the  level control  range for  the
               transmitter so we can use the transmitter for instru-
               mentation as well as control. We can put a long arm on
               the float and produce an output signal proportional to
               almost the full height of the tank so we can tell where
               the level is even when it’s not in the control range. For
               example, our level transmitter could be set to indicate
               levels from zero to 60 inches in the tank. We select our
               control range and adjust the controller gain accordingly.
               If we want the level to control within ten inches we set   Figure 11-6. Totalizer with reset accessories
               the gain of the controller to six. If we establish a set-
               point at fifty inches the control valve will be fully closed     If this looks like an unmanageable concept don’t
               when the level reaches 55 inches and closed at 45 inches.  quit yet. Reset control does some great things and after
               We can also adjust the setpoint to anywhere from five  we get through this discussion you should be able to ap-
               inches to 55. We have to reserve half the control range to  preciate what it does.
               have control, that’s why the setpoint can’t be anywhere     Operation of reset control is difficult to compre-
               within the range of the transmitter when we’re using  hend and I’ve discovered many technicians have an
               proportional control. If we raise the setpoint to, say 58  inappropriate perception of it because they think in
               inches, then we will not be able to stroke the output  terms of speed, not response to an error. The operation
               valve completely.                                    of the ratio totalizer provides a basis of understanding
                    By  now  you’re  asking  how  good  is  a  controller  because  the  dynamic  effects  are  apparent.  Let’s  start
               that needs ten inches to work when it comes to con-  with a steady state condition where the pressure in the
               trolling the water level in a boiler. If we had to use the  output bellows matches the pressure in the reset bellows
               system described we would have to set the gain to sixty  and the error is zero. Assume the process variable drops
               in order to keep the level within an inch of setpoint.  a little so an error is generated. The proportional func-
               There’s two answers to that question, first we normally  tion of the controller responds immediately, changing
               use a maximum of twenty inches for the range of the  the output an amount equal to the error times the gain.
               boiler water level transmitter (even if the boiler is over  Also assume the error isn’t corrected immediately by the
               a hundred feet high) and we’ll add reset to our control-  output change and holds. Since there is now a difference
               ler. There are practical limits to an instrument’s range  between the output and reset bellows control air bleeds
               when it is used for control but reset control is a refine-  through the needle valve to (or from) the volume cham-
               ment that can only be described as beautiful; it makes  ber and reset bellows. Since the error persists the output
               the setpoint realistic.                              will have to continue to change to balance the error. If
                    To convert our controller to a reset controller we  the error continued to exist the output would continue
               add (Figure 11-6) some tubing, a needle valve, and a  to change until it reached its practical limit (zero psig or
               small volume chamber. It’s these reset accessories that  supply pressure).
               make our controller a reset controller. The controller has     That doesn’t happen often, usually the controller
               now acquired dynamic properties. The only time a reset  action results in the process variable returning to the set-
               controller will be in balance is when the setpoint and the  point. That’s the beauty of reset control, it always works
               process variable are precisely the same and the output  to return the process variable to the setpoint, not some
               has stopped changing. With our proportional controller  value that’s offset by the proportional value. It’s real
               the system could be stable with the level holding at a  control. You can see that the only time the controller isn’t
               value below or above the setpoint. Now the left side of  changing its output is when the process variable and set-
               the controller is in balance only when the process vari-  point are exactly the same and the pressure in the output
               able and setpoint are precisely the same, when the error  and reset bellows equal each other. You can also see that
               is zero. Even then the controller output can be changing,  the controller can be in balance with any pressure at the
               when the pressures inside the output and reset bellows  output. The output signal can be anything from zero to
               are different.                                       supply pressure balanced by the same pressure in the re-
   383   384   385   386   387   388   389   390   391   392   393