Page 123 - Chemical process engineering design and economics
P. 123

Process Circuit Analysis                                      107


                 Over  a  small  temperature range,  the  enthalpy  of vaporization  is  essentially
            constant. Thus, we may use the Clausius-Clapyeron equation, Equation  3.2.32, to
            express the  vapor  pressure  of  water  as  a  function  of temperature. Next,  calculate
            the mole  fraction  of water in the exit air using Equation  3.2.28, where p,is, is the
                                                                      2
            vapor pressure  of water  at the  exit-air temperature.  We assume that heat capacity
            of  air  and  water  vapor  is  constant  over  the  temperature  range  of  interest. Using
            data taken  from  Reid  et  al.  [2], calculate  the  heat  capacities  at  100  °F (37.8 °C).
            Thus,  Cp, = 8.2 Btu/lbmol-°F  (34.3 kJ/kg mol-K) and c p2 = 7.2 Btu/lbmol-°F (30.1
            kJ/kg mol-K). The heat capacity of water,  18.0 Btu/lbmol-°F  (75.4 kJ/kg mol-K),
            is  also  assumed  constant.  We  select  32.0 °F  as the  reference  temperature, R,  to
                                                                          t
            correspond  to  the  steam  tables.  Thus,  Equations  37  to  42  in  Table  3.2.2 are  the
            pure component enthalpies of all the components.
                 The next step in the problem solving procedure is to outline a solution pro-
            cedure  for the  Equations  listed in Table 3.2.2.  There  are algorithms available  for
            determining in what order to solve a set of algebraic equations, which is called the
            precedence order.  See, for example, Rudd and Watson [17] and Myers and Seider
            [18]  for a discussion of some  of these algorithms.  Sometimes,  we can develop a
            procedure  by  inspection  of  an  equation  set, as  in  the procedure  given  in  Table
            3.2.3.

            Table 3.2.3  Calculation Procedure -  Cooling-Tower Analysis_______

            1. Obtain pw from the steam tables at tw  (Equation 3.2.30 in Table 3.2.2)
            2. Calculate ym  from Equation 3.2.29.

            3. Obtain Ahw  from the steam tables at tiw, Equation 3.2.31.

            4. Calculate yi,i from the psychrometric relation, Equation 3.2.27.
            5. Assume an exit air temperature, t 2.

            6. Calculate p 2,is from Equations 3.2.32 to 3.2.34.

            7. Calculate y2,i from Equation 3.2.28.
            8. Calculate mi,  m 2  rot, yi  2 and y 22  from Equations 3.2.22 to 3.2.25 and Equation
            3.2.44.

            9. Calculate h-i, h 2, h 3, and h 4 from Equations 3.2.35 to 3.2.43.
            10.  Substitute  h-i,  h 2,  ha, hu,  mi,  m 2, ma, and  m 4  into  Equation  3.2.26  to  check  the
            assumed value of t 2.

            11.  Repeat steps 5 to  10 until Equation 3.2.26 is satisfied within a sufficient  degree
            of accuracy.





         Copyright © 2003 by Taylor & Francis Group LLC
   118   119   120   121   122   123   124   125   126   127   128