Page 290 - Defrosting for Air Source Heat Pump
P. 290

284                                         Defrosting for Air Source Heat Pump


























         Fig. 9.27 Analysis on frost accumulation and defrosting efficiency.


            Fig. 9.27 presents the analysis results on frost accumulation and defrosting effi-
         ciency. The frost accumulation increased with the frosting duration, and reached its
         highest value at 1074 g at 70 min in Case 5. Clearly, the increasing rate was not con-
         stant as time, which was much higher at 50–55 min. Although the defrosting duration
         was prolonged as the increase of frost accumulation, the defrosting efficiency reached
         its highest value at 51.80% in Case 2. That means that after the frost accumulation is
         more than 933 g, the defrosting performance becomes worse and worse as the frost
         accumulation increases. Consequently, the most suitable frost accumulation for good
         defrosting performance comes out around Case 2. Compared with Case 2, the
         defrosting duration was prolonged by 29 s, or 16.2%, and the defrosting efficiency
         decreased by 2.53%, or 5.14%, in Case 5. Although the defrosting efficiency goes
         up when the frost duration is longer, as shown in Fig. 9.25, the COP of the system
         during the frosting stage would adversely degrade due to more frost accumulation.
         Therefore, in this study, the frost accumulation is highly recommended at 933 g for
         defrosting initiation control. It is also suggested as the reference value for the frosting
         termination control strategy.
            In conclusion, an experimental study on time-based defrosting initiation control
         strategy optimization for an ASHP unit with frost evenly distributed and melted frost
         locally drained was conducted, and the study results were analyzed and conclusions
         were reached. To make the frost evenly accumulate on the surface of the multicircuit
         outdoor coil, an experimental setup was designed and carried out. In the three-circuit
         outdoor coil, three water-collecting trays were installed under each circuit during
         defrosting to experimentally validate the frost distribution status. Second, frost accu-
         mulation increased as the frosting duration was prolonged, although it is not at a pos-
         itive proportional relationship. After 50 min into frosting, the frost accumulation
         increased quickly at first, and then much more slowly. In the same interval of
   285   286   287   288   289   290   291   292   293   294   295