Page 291 - Defrosting for Air Source Heat Pump
P. 291

Defrosting control strategy                                       285

           5 min, the frost accumulation increased 128 g, or 15.9%, from Case 1 to Case 2. How-
           ever, the increase of frost accumulation was only 73 g, or 7.3%, from Case 4 to Case 5.
           Additionally, the defrosting duration is also not at a positive proportional relationship
           with the total frost accumulation. The increased frost accumulation prolonged the
           defrosting duration, but the main difference comes at the preheating stage during
           defrosting. When the frost accumulation is 805 g in Case 1, the preheating stage cost
           35 s while it takes 96 s for the frost accumulation to reach 1074 g in Case 5. Finally, in
           view of system stability and indoor thermal comfort, the system performance would
           be degraded when frost accumulation was more than 933 g. In view of defrosting per-
           formance, the defrosting efficiency also reached its peak at 51.80% when the frost
           accumulation was at 933 g. As demonstrated, frost accumulation is the most funda-
           mental reference parameter for initiation defrosting control in an ASHP unit with
           the frost evenly distributed and the melted frost locally drained. Meanwhile, the
           time-based initiation defrosting control was optimized with this method, and thus
           the potential energy waste was expected to be saved.



           9.4   Termination of defrosting control

           In practical applications, an RCD operation can be started based on the surface tem-
           perature of an outdoor coil, the pressure difference across an outdoor coil, or time.
           Among them, terminating a defrosting operation based on the surface temperature
           of an outdoor coil is currently the mostly widely used method [11]. For an outdoor
           coil with one circuit, the cold refrigerant flows from the downside to the upside along
           the tube. And thus, it is easy to understand that more frost accumulates on the down-
           side surface. In order to make sure the melted frost was totally vaporized, the temper-
           ature sensor is always located at the circuit exit for a one-circuit outdoor coil, as shown
           in Fig. 9.28A. However, for an outdoor coil used in an ASHP unit, on its refrigerant
           side, multiple parallel circuits are commonly used for minimized refrigerant pressure
           loss and enhanced heat transfer efficiency. Also, to save more floor space, the mul-
           ticircuit outdoor coil is always vertically installed on the outside wall [18]. During
           RCD, the melted frost would flow downward along the tube wall and fin, which













             (A)                            (B)

           Fig. 9.28 Location of temperature sensors at the two typical outdoor coils. (A) One circuit
           outdoor coil and (B) Multicircuit outdoor coil.
   286   287   288   289   290   291   292   293   294   295   296