Page 300 - Defrosting for Air Source Heat Pump
P. 300

294                                         Defrosting for Air Source Heat Pump



























         Fig. 9.38 Total electricity inputs coming from outside the system during defrosting.




























         Fig. 9.39 Measured refrigerant volumetric flow rate during defrosting.

            The measured temperatures of compressor suction and discharge and the temper-
         atures of the tube surface at the entrance and exit of the outdoor coil during defrosting
         are separately shown in Figs. 9.35 and 9.36. As analyzed in Fig. 9.35, the compressor
                                                       °
         suction temperature will increase to its highest value, 2.6 C, at 170 s into defrosting,
                                            °
         and then decrease to its lowest value,  1.4 C, at 190 s into defrosting. It is demon-
         strated that this period is special, and the most suitable DTT should be at this
   295   296   297   298   299   300   301   302   303   304   305