Page 298 - Defrosting for Air Source Heat Pump
P. 298

292                                         Defrosting for Air Source Heat Pump



























         Fig. 9.34 Measured fin surface temperature at the center of each circuit of the outdoor coil.




























         Fig. 9.35 Measured temperatures of compressor suction and discharge during defrosting.


         transfer process delay from the refrigerant to the tube, and then to the fins. Second, the
         curve of Circuit 3 is not always the lowest in Fig. 9.34, which is different from that
         shown in Fig. 9.33. This is because of the disturbing effects of the downward-flowing
         melted frost, which will cool the temperature sensors by taking latent heat from them.
         As listed in Table 9.9, the fin surface temperature differences at the first five divided