6.54                       CHAPTER SIX

         Example 6.5 illustrates T-beam analysis of a masonry wall section built from nominal 8 ×
         8 × 16 in. concrete masonry units, which is subjected to out-of-plane loads.


         6.7.7  MSJC-08 Provisions for Design of Masonry Walls for
         Out-of-Plane Loads
         MSJC-08 Section 3.3.5.3 presents two different conditions for strength design of walls,
         although the design procedure under both conditions is identical:

         1. When the axial stress due to factored loads is less than or equal to 0.20 ′ f .
                                                               m
         2. When the slenderness ratio exceeds 30 (i.e., h/t > 30), the axial stress due to factored
           loads is required to be less than 0.05 ′ f .
                                      m
           The minimum required thickness of walls is 6 in. nominal. The design procedure sug-
         gested by the MSJC Code is as follows:
         1. The design strength should satisfy the following condition [Eq. (6.17), MSJC-08/3-27]:

                                     M  ≤ f M            (6.17, MSJC-08/3-27)
                                       u    n
           where f = 0.9 is the strength reduction factor.

         2. Calculate the nominal moment strength from Eq. (6.18):
                                                a ⎞
                                M = ( A f +  P ⎜ ) ⎛ d − ⎟  (6.18, MSJC-08/3-28)
                                 n    s y  u  ⎝  ⎠ 2
           where
                                       P +  A f
                                    a =  u  s y          (6.19, MSJC-08/3-29)
                                       008  fb ′
                                        .
                                           m
           The quantity in the numerator of Eq. (6.18) may be considered as effective area of rein-
           forcement given by Eq. (6.20):
                                        P +  A f
                                    A =  u  s y                      (6.20)
                                     se
                                          f y

         3. The nominal shear strength of the wall should be determined as discussed in Chap. 4.
         4. The horizontal midheight deflection d , due to service lateral loads and service axial loads
                                     s
           (without load factors), should be limited to value given by relationship in Eq. (6.21):
                                     d  ≤ 0.007h         (6.21, MSJC-08/3-30)
                                      s
         5. The midheight deflection (assuming that simple-support end conditions apply) is to be
           calculated from Eqs. (6.22) or (6.23) as applicable: