Page 404 - Design of Reinforced Masonry Structures
P. 404

WALLS UNDER GRAVITY AND TRANSVERSE LOADS      6.55

           (a)   When the moment due to service loads is less than the cracking moment (i.e.,
              M  < M )
               ser
                    cr
                                           ser
                                    δ  =  5Mh  2         (6.22, MSJC-08/3-31)
                                     ser
                                        48EI
                                           mg
           (b)   When the service load moment is greater than the cracking moment but less than the
              nominal moment strength M  (i.e., M  < M  < M )
                                  n     cr   ser  n
                                  5Mh 2  5 M(  − M ) h  2
                             δ ser  =  cr  +  ser  cr    (6.23, MSJC-08/3-32)
                                 48EI       48EI  cr
                                    mg
                                               m
           Note that the cracking moment M  is to be determined based on the modulus of
                                     cr
         rupture, f , as discussed in Chap. 4. Values of modulus of rupture are listed in MSJC-08
               r
         Table 3.1.8.2. Note that the moment of inertia of the cracked section would be based on the
         effective area of steel, A , given by Eq. (6.25). The expression for the moment of inertia of
                          se
         the cracked section can be expressed as
                                              −
                                            (
                                 I =  bc  3  + nA d c) 2             (6.24)
                                 cr
                                           se
                                     3
         where  b = 12 in. (unit width of wall)
              c = depth of neutral axis from the compression face of the wall
              d = depth of the centroid of tensile reinforcement
              n = modular ratio, and
                                        P +  A f
                                    A =  u  s y               (6.20 repeated)
                                     se
                                           f
                                           y
           Examples 6.2 and 6.3 illustrate, respectively, analysis and design of reinforced masonry
         walls subjected to out-of-plane loads as discussed above. It would be noted that the basic
         procedure in both cases is identical. Typically, an analysis problem involves checking the
         adequacy of a wall for its capacity to carry gravity and lateral loads, and for deflection, all
         design details of the wall being known. In the case of a typical design problem, all loads
         (gravity and lateral) and eccentricity of gravity load would be known, and the wall thickness
         and its compressive strength dimensions would have been preselected, for example, an 8-in.
                                                                     2
         nominal thick concrete masonry wall and the compressive strength ( ′ f ) of 2000 lb/in. . The
                                                          m
         only unknown to be determined would be the size and spacing of vertical reinforcing bars.
         One can proceed with design by assuming a vertical bar size (e.g., No. 5 or No. 6) and hori-
         zontal spacing of these bars (assuming that the wall is spanning vertically). The calculations
         then would be similar to those in Example 6.2. If the selected bar size and spacing do not
         prove to be adequate, one should try a larger or smaller bar at the same or different spacing

         as necessary. This step should be repeated until a satisfactory design is obtained.
           Example 6.2  A 20-ft-high, 8-in.-nominal, solidly grouted, concrete masonry wall is
           centrally reinforced with No. 6 vertical bars (Grade 60) spaced horizontally at 24 in. on
                                  2
           center. The wall weighs 84 lb/ft  per linear foot of the wall. It carries a superimposed
           dead roof load of 160 lb/ft and a roof live load of 60 lb/ft length of the wall. The roof is
           supported on a ledger beam attached to the wall, which creates an eccentricity of 4 in.
                                                                      2
           from the center line of the wall (Fig. E6.2). The lateral load due to wind is 20 lb/ft  and
                             2
           due to earthquake 42 lb/ft . Check the adequacy of the wall to carry gravity and lateral
                                     2
           loads, and deflection ′ f = 2000 lb/in. .
                           m
   399   400   401   402   403   404   405   406   407   408   409